![NR Electric PCS-9611 Instruction Manual Download Page 277](http://html1.mh-extra.com/html/nr-electric/pcs-9611/pcs-9611_instruction-manual_1713962277.webp)
12 Commissioning
PCS-9611 Feeder Relay
12-5
Date: 2014-04-08
Voltage transformer circuits
Current transformer circuits
DC power supply
Optic-isolated binary inputs
Binary output contacts
Electrical communication ports
The insulation resistance should be greater than 100MΩ at 500V.
Test method:
To unplug all the terminals sockets of this relay, and do the insulation resistance test for each
circuit above with an electronic or brushless insulation tester.
On completion of the insulation resistance tests, ensure all external wiring is correctly reconnected
to the protection.
12.5.1.3 External Wiring
Check that the external wiring is correct to the relevant relay diagram and scheme diagram.
Ensure as far as practical that phasing/phase rotation appears to be as expected.
Check the wiring against the schematic diagram for the installation to ensure compliance with the
customer’s normal practice.
12.5.1.4 Auxiliary Power Supply
The relay only can be operated under the auxiliary power supply depe
nding on the relay’s nominal
power supply rating.
The incoming voltage must be within the operating range specified in
Section 2.1.1.1
, before
energizing the relay, measure the auxiliary supply to ensure it within the operating range.
Other requirements to the auxiliary power supply are specified in
Section 2.1.1.1
. See this section
for further details about the parameters of the power supply.
WARNING!
Energize this relay only when the power supply is within the specified
operating ranges in
Section 2.1.1.1
.
12.5.2 With the Relay Energized
The following groups of checks verify that the relay hardware and software is functioning correctly
and should be carried out with the auxiliary supply applied to the relay.
The current and voltage transformer connections must remain isolated from the relay for these
checks. The trip circuit should also remain isolated to prevent accidental operation of the
associated circuit breaker.
Summary of Contents for PCS-9611
Page 1: ...PCS 9611 Feeder Relay Instruction Manual NR Electric Co Ltd...
Page 2: ......
Page 10: ...1 Introduction PCS 9611 Feeder Relay 1 b Date 2014 04 08...
Page 30: ...2 Technical Data PCS 9611 Feeder Relay 2 14 Date 2014 04 08...
Page 36: ...3 Operation Theory PCS 9611 Feeder Relay 3 f Date 2014 04 08...
Page 108: ...4 Supervision PCS 9611 Feeder Relay 4 b Date 2014 04 08...
Page 116: ...5 Management Function PCS 9611 Feeder Relay 5 b Date 2014 04 08...
Page 120: ...5 Management Function PCS 9611 Feeder Relay 5 4 Date 2014 04 08...
Page 218: ...9 Configurable Function PCS 9611 Feeder Relay 9 b Date 2014 04 08...
Page 232: ...9 Configurable Function PCS 9611 Feeder Relay 9 14 Date 2014 04 08...
Page 262: ...11 Installation PCS 9611 Feeder Relay 11 b Date 2014 04 08...
Page 272: ...12 Commissioning PCS 9611 Feeder Relay 12 b Date 2014 04 08...
Page 292: ...13 Maintenance PCS 9611 Feeder Relay 13 b Date 2014 04 08...
Page 296: ...14 Decommissioning and Disposal PCS 9611 Feeder Relay 14 b Date 2014 04 08...
Page 298: ...14 Decommissioning and Disposal PCS 9611 Feeder Relay 14 2 Date 2014 04 08...
Page 300: ...15 Manual Version History PCS 9611 Feeder Relay 15 2 Date 2014 04 08...