3 Operation Theory
PCS-9611 Feeder Relay
3-31
Date: 2014-04-08
[VTS.En] is the logic setting of the protection voltage transformer supervision function;
[50/51SEF.En_VTS_Blk] is the logic setting of the function which can block all the SEF
protection that relate to the voltage measurement when the voltage transformer is failed;
[BI_En_VT] is the binary input for denoting the local VT is in service;
[VTS.Alm] is the alarm signal of the protection voltage transformer supervision.
3.6.4 Sensitive Earth Fault Protection Settings
All the settings of the sensitive earth fault protection are listed in the following table. For the
information about the common explanation of the settings, see
Section 7.3
.
No.
Menu text
Explanation
Range
Step
1
50/51SEF.RCA
The relay characteristic angle for the directional
sensitive earth fault protection
-180°~179°
1°
2
50/51SEF.En_VTS_Blk
The logic setting of the function which blocks the
SEF protection related voltage measurement
when the voltage transformer is failed
0~1
1
3
50/51SEF1.3I0_Set
The current setting of the stage 1 sensitive earth
fault protection
0.005~1.0A
0.001A
4
50/51SEF1.t_Op
The time setting of the stage 1 sensitive earth
fault protection
0~100s
0.001s
5
50/51SEF1.Opt_Dir
The setting is used to select the directional mode
for the stage 1 SEF protection, see
Section 3.6.3
0~2
1
6
50/51SEF1.En
The logic setting of the s tage 1 sensitive earth
fault protection
0~1
1
7
50/51SEF1.OutMap
The output matrix setting of the stage 1 sensitive
earth fault protection
0x00000 ~
0xFFFFF
1
8
50/51SEF2.3I0_Set
The current setting of the stage 2 sensitive earth
fault protection
0.005~1.0A
0.001A
9
50/51SEF2.t_Op
The time setting of the stage 2 sensitive earth
fault protection
0~100s
0.001s
10
50/51SEF2.Opt_Dir
The setting is used to select the directional mode
for the stage 2 SEF protection, see
Section 3.6.3
0~2
1
11
50/51SEF2.En
The logic setting of the stage 2 sensitive earth
fault protection
0~1
1
12
50/51SEF2.OutMap
The output matrix setting of the stage 2 sensitive
earth fault protection
0x00000 ~
0xFFFFF
1
13
50/51SEF3.3I0_Set
The current setting of the stage 3 sensitive earth
fault protection
0.005~1.0A
0.001A
14
50/51SEF3.t_Op
The time setting of the stage 3 sensitive earth
fault protection
0~100s
0.001s
15
50/51SEF3.Opt_Dir
The setting is used to select the directional mode
for the stage 3 SEF protection, see
Section 3.6.3
0~2
1
Summary of Contents for PCS-9611
Page 1: ...PCS 9611 Feeder Relay Instruction Manual NR Electric Co Ltd...
Page 2: ......
Page 10: ...1 Introduction PCS 9611 Feeder Relay 1 b Date 2014 04 08...
Page 30: ...2 Technical Data PCS 9611 Feeder Relay 2 14 Date 2014 04 08...
Page 36: ...3 Operation Theory PCS 9611 Feeder Relay 3 f Date 2014 04 08...
Page 108: ...4 Supervision PCS 9611 Feeder Relay 4 b Date 2014 04 08...
Page 116: ...5 Management Function PCS 9611 Feeder Relay 5 b Date 2014 04 08...
Page 120: ...5 Management Function PCS 9611 Feeder Relay 5 4 Date 2014 04 08...
Page 218: ...9 Configurable Function PCS 9611 Feeder Relay 9 b Date 2014 04 08...
Page 232: ...9 Configurable Function PCS 9611 Feeder Relay 9 14 Date 2014 04 08...
Page 262: ...11 Installation PCS 9611 Feeder Relay 11 b Date 2014 04 08...
Page 272: ...12 Commissioning PCS 9611 Feeder Relay 12 b Date 2014 04 08...
Page 292: ...13 Maintenance PCS 9611 Feeder Relay 13 b Date 2014 04 08...
Page 296: ...14 Decommissioning and Disposal PCS 9611 Feeder Relay 14 b Date 2014 04 08...
Page 298: ...14 Decommissioning and Disposal PCS 9611 Feeder Relay 14 2 Date 2014 04 08...
Page 300: ...15 Manual Version History PCS 9611 Feeder Relay 15 2 Date 2014 04 08...