3 Operation Theory
PCS-9611 Feeder Relay
3-29
Date: 2014-04-08
“t
SEF1
” is the setting [50/51SEF1.t_Op], the time setting of the SEF1 protection;
[50/51SEF1.En] is the logic setting of the stage 1 sensitive earth fault protection;
[50/51SEF1.En1] is the binary signal for enabling the stage 1 sensitive earth fault protection;
[50/51SEF1.Blk] is the binary signal for blocking the stage 1 sensitive earth fault protection;
“50/51SEF1.Dir” denotes the status of the directional element for the stage 1 sensitive earth
fault protection, see
Section 3.6.3
for more details about the directional element.
3.6.2 IDMT Sensitive Earth Fault Protection
The stage 4 sensitive earth fault protection also can be used as inverse definite minimum time
(IDMT) sensitive earth fault protection. It has the same inverse time characteristic with the IDMT
overcurrent protection (see
Section 3.3.2
), and the setting [50/51SEF4.Opt_Curve] can be used to
select the expected curve.
The logic diagram of the IDMT sensitive earth fault protection is shown as below. The sensitive
earth fault current block is a level detector that detects whether the current magnitude is above
the threshold.
[50/51G4.En]
[50/51G4.En1]
[50/51G4.Opt_Curve] = 0
&
50/51G4.HmBlk
50/51G4.Dir
&
[50/51G4.Op]
I
01
> [50/51G4.3I0_Set]
[50/51G4.Blk]
[50/51G4.St]
IDMT
Figure 3.6-2 Logic diagram of the IDMT sensitive earth fault protection
Where:
[50/51SEF4.3I0_Set] is the current setting of the stage 4 sensitive earth fault protection;
[50/51SEF4.En] is the logic setting of the stage 4 sensitive earth fault protection;
[50/51SEF4.En1] is the binary signal for enabling the stage 4 sensitive earth fault protection;
[50/51SEF4.Blk] is the binary signal for blocking the stage 4 sensitive earth fault protection;
[50/51SEF4.Opt_Curve] is the setting for selecting the inverse time characteristic curve ;
“50/51SEF4.Dir” denotes the status of the directional element for the stage 4 sensitive earth
fault protection, see
Section 3.6.3
for more details about the directional element.
3.6.3 Directional Element for Sensitive Earth Fault Protection
The residual voltage is used to polarize the directional element for the SEF protection. With earth
fault protection, the polarizing signal is required to be a representative of the earth fault condition.
As residual voltage is generated during earth fault conditions, this quantity is commonly used to
polarize directional elements. The residual voltage is also derived from the 3-phase voltage input,
which are same with the directional element for the zero sequence overcurrent protection.
Summary of Contents for PCS-9611
Page 1: ...PCS 9611 Feeder Relay Instruction Manual NR Electric Co Ltd...
Page 2: ......
Page 10: ...1 Introduction PCS 9611 Feeder Relay 1 b Date 2014 04 08...
Page 30: ...2 Technical Data PCS 9611 Feeder Relay 2 14 Date 2014 04 08...
Page 36: ...3 Operation Theory PCS 9611 Feeder Relay 3 f Date 2014 04 08...
Page 108: ...4 Supervision PCS 9611 Feeder Relay 4 b Date 2014 04 08...
Page 116: ...5 Management Function PCS 9611 Feeder Relay 5 b Date 2014 04 08...
Page 120: ...5 Management Function PCS 9611 Feeder Relay 5 4 Date 2014 04 08...
Page 218: ...9 Configurable Function PCS 9611 Feeder Relay 9 b Date 2014 04 08...
Page 232: ...9 Configurable Function PCS 9611 Feeder Relay 9 14 Date 2014 04 08...
Page 262: ...11 Installation PCS 9611 Feeder Relay 11 b Date 2014 04 08...
Page 272: ...12 Commissioning PCS 9611 Feeder Relay 12 b Date 2014 04 08...
Page 292: ...13 Maintenance PCS 9611 Feeder Relay 13 b Date 2014 04 08...
Page 296: ...14 Decommissioning and Disposal PCS 9611 Feeder Relay 14 b Date 2014 04 08...
Page 298: ...14 Decommissioning and Disposal PCS 9611 Feeder Relay 14 2 Date 2014 04 08...
Page 300: ...15 Manual Version History PCS 9611 Feeder Relay 15 2 Date 2014 04 08...