![NR Electric PCS-9611 Instruction Manual Download Page 164](http://html1.mh-extra.com/html/nr-electric/pcs-9611/pcs-9611_instruction-manual_1713962164.webp)
7 Settings
PCS-9611 Feeder Relay
7-20
Date: 2014-04-08
7.3.13 Frequency Protection Settings
The frequency protection settings (in the submenu
“
FreqProt Settings
”) are used to determine
the characteristic of the frequency protection.
All the settings of the frequency protection are listed in the following table.
No.
Menu text
Explanation
Range
Step
1
81.Upp_VCE
The setting of the low voltage blocking element of
the frequency protection (phase-to-phase voltage)
10~120V
0.001V
2
81U1.f_Set
The
frequency
setting
of
the
stage
1
under-frequency protection
45~60Hz
0.001Hz
3
81U1.t_Op
The time setting of the stage 1 under-frequency
protection
0~100s
0.001s
4
81U1.En
The logic setting of the stage 1 under-frequency
protection
0~1
1
5
81U1.OutMap
The output matrix setting of the stage 1
under-frequency protection
0x00000 ~
0xFFFFF
1
6
81U2.f_Set
The
frequency
setting
of
the
stage
2
under-frequency protection
45~60Hz
0.001Hz
7
81U2.t_Op
The time setting of the stage 2 under-frequency
protection
0~100s
0.001s
8
81U2.En
The logic setting of the stage 2 under-frequency
protection
0~1
1
9
81U2.OutMap
The output matrix setting of the stage 2
under-frequency protection
0x00000 ~
0xFFFFF
1
10
81U3.f_Set
The
frequency
setting
of
the
stage
3
under-frequency protection
45~60Hz
0.001Hz
11
81U3.t_Op
The time setting of the stage 3 under-frequency
protection
0~100s
0.001s
12
81U3.En
The logic setting of the stage 3 under-frequency
protection
0~1
1
13
81U3.OutMap
The output matrix setting of the stage 3
under-frequency protection
0x00000 ~
0xFFFFF
1
14
81U4.f_Set
The
frequency
setting
of
the
stage
4
under-frequency protection
45~60Hz
0.001Hz
15
81U4.t_Op
The time setting of the stage 4 under-frequency
protection
0~100s
0.001s
16
81U4.En
The logic setting of the stage 4 under-frequency
protection
0~1
1
17
81U4.OutMap
The output matrix setting of the stage 4
under-frequency protection
0x00000 ~
0xFFFFF
1
18
81O1.f_Set
The
frequency
setting
of
the
stage
1
over-frequency protection
50~65Hz
0.001Hz
Summary of Contents for PCS-9611
Page 1: ...PCS 9611 Feeder Relay Instruction Manual NR Electric Co Ltd...
Page 2: ......
Page 10: ...1 Introduction PCS 9611 Feeder Relay 1 b Date 2014 04 08...
Page 30: ...2 Technical Data PCS 9611 Feeder Relay 2 14 Date 2014 04 08...
Page 36: ...3 Operation Theory PCS 9611 Feeder Relay 3 f Date 2014 04 08...
Page 108: ...4 Supervision PCS 9611 Feeder Relay 4 b Date 2014 04 08...
Page 116: ...5 Management Function PCS 9611 Feeder Relay 5 b Date 2014 04 08...
Page 120: ...5 Management Function PCS 9611 Feeder Relay 5 4 Date 2014 04 08...
Page 218: ...9 Configurable Function PCS 9611 Feeder Relay 9 b Date 2014 04 08...
Page 232: ...9 Configurable Function PCS 9611 Feeder Relay 9 14 Date 2014 04 08...
Page 262: ...11 Installation PCS 9611 Feeder Relay 11 b Date 2014 04 08...
Page 272: ...12 Commissioning PCS 9611 Feeder Relay 12 b Date 2014 04 08...
Page 292: ...13 Maintenance PCS 9611 Feeder Relay 13 b Date 2014 04 08...
Page 296: ...14 Decommissioning and Disposal PCS 9611 Feeder Relay 14 b Date 2014 04 08...
Page 298: ...14 Decommissioning and Disposal PCS 9611 Feeder Relay 14 2 Date 2014 04 08...
Page 300: ...15 Manual Version History PCS 9611 Feeder Relay 15 2 Date 2014 04 08...