3 Operation Theory
PCS-9611 Feeder Relay
3-24
Date: 2014-04-08
“I
012
” is the 2
nd
harmonic of the No.1 zero sequence current.
3.5.5 Zero Sequence Overcurrent Protection Settings
For the information about the common explanation of the settings, see
Section 7.3
.
All the settings of the No.1 zero sequence overcurrent protection are listed in the following table.
No.
Menu text
Explanation
Range
Step
1
50/51G.RCA
The relay characteristic angle for the No.1
directional zero sequence overcurrent protection
-180°~179°
1°
2
50/51G.En_VTS_Blk
The logic setting of the function which blocks the
1ROC protection related voltage measurement
when the voltage transformer is failed
0~1
1
3
50/51G.K_Hm2
The percent setting of the harmonic blocking
element for the No.1 ROC protection
0.05~1.00
0.001
4
50/51G.3I0_Rls_HmBlk
The current setting for releasing the harmonic
blocking element of the No.1 ROC protection
0.05In~30In
0.001A
5
50/51G1.3I0_Set
The current s etting of the No.1 stage 1 zero
sequence overcurrent protection
0.05In~30In
0.001A
6
50/51G1.t_Op
The time s etting of the No.1 stage 1 zero
sequence overcurrent protection
0~100s
0.001s
7
50/51G1.Opt_Dir
The setting is used to select the directional mode
for the No.1 ROC1 protection, see
Section 3.5.3
0~2
1
8
50/51G1.En_Hm_Blk
The logic setting of the harmonic blocking element
for the No.1 ROC1 protection
0~1
1
9
50/51G1.En
The logic setting of the No.1 stage 1 zero
sequence overcurrent protection
0~1
1
10
50/51G1.OutMap
The output matrix setting of the No.1 stage 1 zero
sequence overcurrent protection
0x00000 ~
0xFFFFF
1
11
50/51G2.3I0_Set
The current s etting of the No.1 stage 2 zero
sequence overcurrent protection
0.05In~30In
0.001A
12
50/51G2.t_Op
The time s etting of the No.1 stage 2 zero
sequence overcurrent protection
0~100s
0.001s
13
50/51G2.Opt_Dir
The setting is used to select the directional mode
for the No.1 ROC2 protection, see
Section 3.5.3
0~2
1
14
50/51G2.En_Hm_Blk
The logic setting of the harmonic blocking element
for the No.1 ROC2 protection
0~1
1
15
50/51G2.En
The logic setting of the No.1 stage 2 zero
sequence overcurrent protection
0~1
1
16
50/51G2.OutMap
The output matrix setting of the No.1 stage 2 zero
sequence overcurrent protection
0x00000 ~
0xFFFFF
1
17
50/51G3.3I0_Set
The current s etting of the No.1 stage 3 zero
sequence overcurrent protection
0.05In~30In
0.001A
Summary of Contents for PCS-9611
Page 1: ...PCS 9611 Feeder Relay Instruction Manual NR Electric Co Ltd...
Page 2: ......
Page 10: ...1 Introduction PCS 9611 Feeder Relay 1 b Date 2014 04 08...
Page 30: ...2 Technical Data PCS 9611 Feeder Relay 2 14 Date 2014 04 08...
Page 36: ...3 Operation Theory PCS 9611 Feeder Relay 3 f Date 2014 04 08...
Page 108: ...4 Supervision PCS 9611 Feeder Relay 4 b Date 2014 04 08...
Page 116: ...5 Management Function PCS 9611 Feeder Relay 5 b Date 2014 04 08...
Page 120: ...5 Management Function PCS 9611 Feeder Relay 5 4 Date 2014 04 08...
Page 218: ...9 Configurable Function PCS 9611 Feeder Relay 9 b Date 2014 04 08...
Page 232: ...9 Configurable Function PCS 9611 Feeder Relay 9 14 Date 2014 04 08...
Page 262: ...11 Installation PCS 9611 Feeder Relay 11 b Date 2014 04 08...
Page 272: ...12 Commissioning PCS 9611 Feeder Relay 12 b Date 2014 04 08...
Page 292: ...13 Maintenance PCS 9611 Feeder Relay 13 b Date 2014 04 08...
Page 296: ...14 Decommissioning and Disposal PCS 9611 Feeder Relay 14 b Date 2014 04 08...
Page 298: ...14 Decommissioning and Disposal PCS 9611 Feeder Relay 14 2 Date 2014 04 08...
Page 300: ...15 Manual Version History PCS 9611 Feeder Relay 15 2 Date 2014 04 08...