3.13 Overvoltage Protection
3.13.1 Overvoltage Protection Theory
This relay provides a two-stage overvoltage protection with definite time delay characteristics. The
two stages have same protection logics. Each stage can be used for tripping or alarming through
the PCS-Explorer and the default is for tripping.
This protection can support all kinds of VT connection: three phase voltage (Ua, Ub, Uc), three
phase-to-phase voltages (Uab, Ubc, Uca), two phase-to-phase voltages (Uab, Ubc), anyone of
three phase voltages or anyone of three phase-to-phase voltages.
Two methods are used to check the overvoltage condition by the setting [59P.Opt_1P/3P]. If
setting [59P.Opt_1P/3P] is set as
“0”, and all of the three voltage values are greater than the
voltage setting, the overvoltage protection will operates after the appointed time delay; and if the
setting [59P.Opt_1P/3P] is set as
“1”, and anyone of the three voltage values is greater than the
voltage setting, the overvoltage protection will operates after the appointed time delay.
The setting [59P.Opt_Up/Upp] is used to decide the voltage input mode. If it is set as
“1”, the input
voltage is phase-to-phase voltage; and if it is set as
“0”, the input voltage is phase voltage. So the
voltage setting must be set in accordance with the setting [59P.Opt_Up/Upp]; i.e. if the setting
[59P.Opt_Up/Upp] is set as
“1”, the voltage setting is set according to phase-to-phase voltage;
and if the setting [59P.Opt_Up/Upp] is set as
“0”, the voltage setting is set according to phase
voltage.
The following figure shows the logic diagram of the stage 1 overvoltage protection.
&
[59P1.En]
[59P.Opt_Up/Upp]
&
Uca > [59P1.U_Set]
Uab > [59P1.U_Set]
Ubc > [59P1.U_Set]
Uca > [59P1.U_Set]
Uab > [59P1.U_Set]
Ubc > [59P1.U_Set]
[59P.Opt_1P/3P]
&
&
&
Uc > [59P1.U_Set]
Ua > [59P1.U_Set]
Ub > [59P1.U_Set]
Uc > [59P1.U_Set]
Ua > [59P1.U_Set]
Ub > [59P1.U_Set]
&
&
[59P1.En1]
[59P1.Blk]
[59P1.Op]
[59P1.St]
t
OV1
0
Figure 3.13-1 Logic diagram of the stage 1 overvoltage protection
Where:
[59P1.U_Set] is the voltage setting of the stage 1 overvoltage protection;
“t
OV1
” is the setting [59P1.t_Op], the time setting of the stage 1 overvoltage protection;
Summary of Contents for PCS-9611
Page 1: ...PCS 9611 Feeder Relay Instruction Manual NR Electric Co Ltd...
Page 2: ......
Page 10: ...1 Introduction PCS 9611 Feeder Relay 1 b Date 2014 04 08...
Page 30: ...2 Technical Data PCS 9611 Feeder Relay 2 14 Date 2014 04 08...
Page 36: ...3 Operation Theory PCS 9611 Feeder Relay 3 f Date 2014 04 08...
Page 108: ...4 Supervision PCS 9611 Feeder Relay 4 b Date 2014 04 08...
Page 116: ...5 Management Function PCS 9611 Feeder Relay 5 b Date 2014 04 08...
Page 120: ...5 Management Function PCS 9611 Feeder Relay 5 4 Date 2014 04 08...
Page 218: ...9 Configurable Function PCS 9611 Feeder Relay 9 b Date 2014 04 08...
Page 232: ...9 Configurable Function PCS 9611 Feeder Relay 9 14 Date 2014 04 08...
Page 262: ...11 Installation PCS 9611 Feeder Relay 11 b Date 2014 04 08...
Page 272: ...12 Commissioning PCS 9611 Feeder Relay 12 b Date 2014 04 08...
Page 292: ...13 Maintenance PCS 9611 Feeder Relay 13 b Date 2014 04 08...
Page 296: ...14 Decommissioning and Disposal PCS 9611 Feeder Relay 14 b Date 2014 04 08...
Page 298: ...14 Decommissioning and Disposal PCS 9611 Feeder Relay 14 2 Date 2014 04 08...
Page 300: ...15 Manual Version History PCS 9611 Feeder Relay 15 2 Date 2014 04 08...