8 Human Machine Interface
PCS-9611 Feeder Relay
8-28
Date: 2014-04-08
3. Press key
“▲” or “▼” to locate the cursor on the submenu “
Device
Test
” and press key “
ENT
”
to enter this submenu.
4. Press key
“▲” or “▼” to locate the cursor on the submenu “
Disturb Events
” and press key
“
ENT
” to enter this submenu.
5. Press key
“▲” or “▼” to locate the cursor on the submenu “
Select Test
” and press key “
ENT
”
to show all the protective elements.
6. Press key
“▲” or “▼” to locate the cursor on a selected protective element and then press key
“
ENT
” to create a binary signal.
NOTE!
The submenu “
All Test
” is used to test all the binary signals automatically.
8.2.10.2 Communication Test of the Telemetering
Operating steps:
1. Press key
“▲” to enter the main menu in the default displaying situation.
2. Press key
“▲” or “▼” to locate the cursor on the submenu “
Test
” and press key “
ENT
” to
enter this submenu.
3. Press key
“▲” or “▼” to locate the cursor on the submenu “
Device
Test
” and press key “
ENT
”
to enter this submenu.
4. Press key
“▲” or “▼” to locate the cursor on the submenu “
Measurements
” and press key
“
ENT
” to all the metering measurements.
5. Press key
“▲” or “▼” to locate the cursor on a selected metering measurements and press
key
“
+
” or “
-
” to modify the selected metering value.
6. After finishing the modification, press key
“
ENT
” to transmit the metering values.
8.2.11
Submenu of “Clock”
Purpose:
This menu is used to modify the current time of this relay.
Access approach:
M
ove cursor to the item “
Clock
” and press key “
ENT
” to enter the clock modification interface after
entering the main menu of this device.
8.2.11.1 Clock Modification
Set the current time of this relay as following steps.
Operating steps:
1. Press key
“▲” to enter the main menu in the default displaying situation.
2. Press key
“▲” or “▼” to locate the cursor on the submenu “
Clock
” and press key “
ENT
” to
Summary of Contents for PCS-9611
Page 1: ...PCS 9611 Feeder Relay Instruction Manual NR Electric Co Ltd...
Page 2: ......
Page 10: ...1 Introduction PCS 9611 Feeder Relay 1 b Date 2014 04 08...
Page 30: ...2 Technical Data PCS 9611 Feeder Relay 2 14 Date 2014 04 08...
Page 36: ...3 Operation Theory PCS 9611 Feeder Relay 3 f Date 2014 04 08...
Page 108: ...4 Supervision PCS 9611 Feeder Relay 4 b Date 2014 04 08...
Page 116: ...5 Management Function PCS 9611 Feeder Relay 5 b Date 2014 04 08...
Page 120: ...5 Management Function PCS 9611 Feeder Relay 5 4 Date 2014 04 08...
Page 218: ...9 Configurable Function PCS 9611 Feeder Relay 9 b Date 2014 04 08...
Page 232: ...9 Configurable Function PCS 9611 Feeder Relay 9 14 Date 2014 04 08...
Page 262: ...11 Installation PCS 9611 Feeder Relay 11 b Date 2014 04 08...
Page 272: ...12 Commissioning PCS 9611 Feeder Relay 12 b Date 2014 04 08...
Page 292: ...13 Maintenance PCS 9611 Feeder Relay 13 b Date 2014 04 08...
Page 296: ...14 Decommissioning and Disposal PCS 9611 Feeder Relay 14 b Date 2014 04 08...
Page 298: ...14 Decommissioning and Disposal PCS 9611 Feeder Relay 14 2 Date 2014 04 08...
Page 300: ...15 Manual Version History PCS 9611 Feeder Relay 15 2 Date 2014 04 08...