534
2.
Click the
button and enter the values in "Switch 1" to "Switch 5".
Enter values within the ranges listed in the tables below.
If any of the values set for switches 1 to 3 is outside the range, the master/local module will start as a master
station (offline mode) of network number 1, resulting in an error. The error details are stored in Switch setting
parameter check result (address: 7BFD
H
).
If the switch 4 is outside the range, the error code is stored in Parameter communication result (address:
7BFE
H
) when the program is executed.
• Setting parameters for the master station
• Setting parameters for the submaster station
*1
The submaster station once needs to perform data link with the master station. Otherwise, the submaster station does
not start its operation.
Item
Description
Setting range
Switch 1
Enter the network number.
0001
H
to 00EF
H
Switch 2
Enter "0000
H
".
0000
H
(Fixed)
Switch 3
Switch 4
(1) When not using the submaster function
Enter 0000
H
.
(2) When using the submaster function
Set the operating status of the master station when it returns.
0000
H
: Returns as a master station
0002
H
: Returns as a submaster station
0000
H
, 0002
H
Switch 5
Enter "0000
H
".
0000
H
(Fixed)
Item
Description
Setting range
Switch 1
Enter the network number.
0001
H
to 00EF
H
Switch 2
Enter the station number.
4101
H
to 4178
H
(Station number: 1 to 120)
Switch 3
Enter "0000
H
".
0000
H
(Fixed)
Switch 4
Select whether to set parameters for the submaster station using a program.
When "Parameters not set" is selected, the submaster station operates with
the parameters set for the master station.
*1
When "Parameters set" is selected, the submaster station operates with the
parameters set using a program.
0000
H
: Parameters not set
0004
H
: Parameters set
0000
H
, 00004
H
Switch 5
Enter "0000
H
".
0000
H
(Fixed)
0
0
H
Network No.: 01
H
to EF
H
(1 to 239)
0
0
H
Network No.: 01
H
to EF
H
(1 to 239)
1
4
H
Station No.: 01
H
to 78
H
(1 to 120)