![Mitsubishi Electric QJ71GF11-T2 User Manual Download Page 424](http://html.mh-extra.com/html/mitsubishi-electric/qj71gf11-t2/qj71gf11-t2_user-manual_1811847424.webp)
422
(b) REMFR/REMTO instruction (
Page 333, Section 10.13, Page 338, Section 10.14)
1.
Set the following registers before executing the REMFR/REMTO instructions:
• Number of resends (REMFR/REMTO) (SW001A)
• Response wait timer (REMFR/REMTO) (SW001B)
2.
When the REMFR/REMTO instruction is executed, the execution status is stored in Execution
status (REMFR/REMTO) (SW0080 to SW009F)
.
(c) RIRD instruction and RIWT instruction (
Page 343, Section 10.15, Page 351,
The arrival monitoring time of the instruction is set using Arrival monitoring time (RIRD/RIWT) (SW0009).
The number of resends for the instruction is set using Number of resends (RIRD/RIWT) (SW000B).
(d) Common link dedicated instructions (except for the REMFR and REMTO
instructions)
Processing results of link dedicated instructions can be checked using Send/receive instruction (1) processing
result (SW0030) for channel 1 and Send/receive instruction (2) processing result (SW0031) for channel 2.
Number
Description
Number
Description
SW001A
Number of resends (REMFR/REMTO)
SW001B
Response wait timer (REMFR/REMTO)
SW0080 to
SW009F
Execution status (REMFR/REMTO)
Number
Description
Number
Description
SW0009
Arrival monitoring time (RIRD/RIWT)
SW000B
Number of resends (RIRD/RIWT)
Number
Description
Number
Description
SW0030
Send/receive instruction (1) processing result
SW0031
Send/receive instruction (2) processing result