CHAPTER 12 TROUBLESHOOTING
12
12.
5
E
rror
Code
List
D207
H
Invalid number of relays in transient
transmission
• Change the system configuration so that the number of relay stations may
be seven or less.
• Check if the routing parameters are correctly set.
• When the IP communication test is executed, change the IP address in
the "Communication Target" so that the number of relay stations may be
127 or less.
D208
H
Network No. error in transient
transmission
• Correct the network number at the request source, and retry the
operation.
• If the request source is on another network, check if the routing
parameters are correctly set.
D209
H
Target station No. error in transient
transmission
Correct the target station number at the request source, and retry the
operation.
D20A
H
Target station No. error in transient
transmission
D20B
H
Specified master station No. error in
transient transmission
D20C
H
Current master station No. error in
transient transmission
D20D
H
Transient data transmission
completion wait timeout
• Check the network status using the CC-Link IE Field Network diagnostics
of the programming tool.
• When the own station, target station, or relay station detected an error,
identify the cause of the error and take action.
• Reduce the frequency of transient transmission, and retry the operation.
• When the mode of the master station (submaster station) is "Online (High
Speed Mode)", change it to "Online (Normal Mode)" and retry the
operation.
• Check if the switching hub and the cables at the request source are
connected properly.
D20E
H
Header information error in transient
transmission
Correct the header information at the request source, and retry the
operation.
D20F
H
Target station No. error in transient
transmission
Check that the command can be requested to all or a group of stations at the
request source, and retry the operation.
D210
H
Target station No. error in transient
transmission
Correct the header information at the request source, and retry the
operation.
D211
H
Own station No. not set (dedicated
instruction)
Set the station number in the parameter setting, and retry the operation.
D212
H
Transient transmission failed
• Check if the switching hub and the cables at the request source are
connected properly.
• Connect the cable to the other port on the request source, and retry the
operation.
• Reduce the frequency of transient transmission, and retry the operation.
D213
H
Transient data command error
• Correct the request command at the request source, and retry the
operation.
• Check the first five digits of the serial number of the master/local module.
If the module does not support the used function, replace it with the
module with the latest version.
D214
H
Transient data length error
Correct the data length at the request source, and retry the operation.
D215
H
Transient data request error
Change the mode to Online, and retry the operation.
D216
H
and D217
H
Transient data command error
Correct the request command at the request source, and retry the operation.
D218
H
Incorrect number of read/write
transient data
Correct the number of read/write device data at the request source, and retry
the operation.
D219
H
Transient data attribute code error
Correct the attribute code at the request source, and retry the operation.
D21A
H
Transient data access code error
Correct the access code at the request source, and retry the operation.
Error code
Error
Action