CHAPTER 9 CC-LINK IE FIELD NETWORK DIAGNOSTICS
9
9.
7
S
e
tting/
Ca
nceling T
e
mpor
ary
Err
o
r I
n
valid S
tat
ion
9.7
Setting/Canceling Temporary Error Invalid Station
A slave station not set as an error invalid station can be temporarily set as an error invalid station. This function is used
to temporarily prevent detection of an error in a slave station.
This function also cancels temporary error invalid station setting configured to a slave station.
(1) Selecting the target module in "Network Status"
(a) Temporary error invalid station setting
(b) Canceling temporary error invalid station setting
1.
Connect GX Works2 to the CPU module.
2.
Start the CC-Link IE Field Network diagnostics from
the menu.
[Diagnostics]
[CC IE Field Diagnostics]
3.
In "Network Status", right-click the icon of the
station for which temporary error invalid station
setting is to be configured. Click [Temporary Error
Invalid Station Setting In Selected Station].
The text background turns yellow. The target station is
temporarily set as an error invalid station.
1.
In "Network Status", right-click the icon of the
station for which temporary error invalid station
setting is to be cancelled. Click [Temporary Error
Invalid Station Setting In Selected Station].
The text background turns white.
The temporary error invalid station setting is cancelled.