442
D0E3
H
Own station No. out of range
Add the station information of the own station in the network configuration
settings of the master station (submaster station).
D0E4
H
Multiple master stations (including own
station)
• Check the network status using the CC-Link IE Field Network diagnostics
of the programming tool.
• Check if the cables and the switching hub are connected properly.
• After taking the above actions, power off and on all the stations where this
error has been detected or reset them.
D0E5
H
Multiple submaster stations (including
own station)
• Check the network status using the CC-Link IE Field Network diagnostics
of the programming tool.
• Check if the cables and the switching hub are connected properly.
• After taking the above actions, power off and on all the stations where this
error has been detected or reset them.
D0F0
H
Network module failure
• A malfunction may have occurred due to noise. Check the wire and cable
distances and grounding condition of each device, and take measures
against noise.
• Execute hardware and self-loopback tests. If a failure occurs again, the
hardware of the master/local module may be faulty. Please consult your
local Mitsubishi representative.
D100
H
and D101
H
Network module failure
• A malfunction may have occurred due to noise. Check the wire and cable
distances and grounding condition of each device, and take measures
against noise.
• Execute hardware and self-loopback tests. If a failure occurs again, the
hardware of the master/local module may be faulty. Please consult your
local Mitsubishi representative.
D110
H
to D113
H
Network module failure
• A malfunction may have occurred due to noise. Check the wire and cable
distances and grounding condition of each device, and take measures
against noise.
• Execute hardware and self-loopback tests. If a failure occurs again, the
hardware of the master/local module may be faulty. Please consult your
local Mitsubishi representative.
D200
H
Transient data received twice
• Check the network status using the CC-Link IE Field Network diagnostics
of the programming tool.
• Check if the cables and the switching hub are connected properly.
• If the request source resides in another network, check if the routing
parameters are correctly set, and take corrective action.
D201
H
Header information error in transient
transmission
Correct the header information at the request source, and retry the
operation.
D202
H
Send buffer full
• Reduce the frequency of transient transmission, and retry the operation.
• When the mode of the master station (submaster station) is "Online (High
Speed Mode)", change it to "Online (Normal Mode)" and retry the
operation.
• Check if the cables and the switching hub are connected properly.
D203
H
Read/write address error in transient
transmission
Correct the read/write address at the request source, and retry the
operation.
D204
H
Network No. error in transient
transmission
• Correct the network number at the request source, and retry the
operation.
• If the request source is on another network, check if the routing
parameters are correctly set.
D205
H
Target station No. error in transient
transmission
Correct the target station number at the request source, and retry the
operation.
D206
H
Network No. error in transient
transmission
• Correct the network number at the request source, and retry the
operation.
• If the request source is on another network, check if the routing
parameters are correctly set.
Error code
Error
Action