![Mitsubishi Electric QJ71GF11-T2 User Manual Download Page 294](http://html.mh-extra.com/html/mitsubishi-electric/qj71gf11-t2/qj71gf11-t2_user-manual_1811847294.webp)
292
(c) SEND instruction setting
The following table lists values set in SEND instruction control data.
Device
Item
Set value
(S1)+0
D350
Execution/abnormal end type
0081
H
(With arrival confirmation, sets data for
abnormal end)
(S1)+1
D351
Completion status
(The system sets this item.)
(S1)+2
D352
Channels used by own station
1
(S1)+3
D353
Target station's channel
2
(S1)+4
D354
Target station's network No.
1
(S1)+5
D355
Target station number
2
(S1)+6
D356
(Unused)
0
(S1)+7
D357
Number of resends
5 times
(S1)+8
D358
Arrival monitoring time
0 (10 seconds)
(S1)+9
D359
Send data length
4 words
(S1)+10
D360
(Unused)
0
(S1)+11
D361
Clock set flag
(The system sets these items.)
(S1)+12 to
(S1)+15
D362 to D365
Clock data of abnormal end
(S1)+16
D366
Error-detected station's
network No.
(S1)+17
D367
Error-detected station number