CHAPTER 10 DEDICATED INSTRUCTIONS
10
10.
4
J
P
/G
P
.R
EA
D (Re
adi
ng
Dat
a
f
rom
t
he P
rogram
mable
Cont
ro
ller
on
Anot
her S
tat
ion)
(a) Control data
Device
Item
Setting data
Setting range
Set by
(S1)+0
Abnormal end
type
1) Abnormal end type (bit 7)
Specify the set status of data in case of abnormal end.
0: After (S1)+11, no data is set for abnormal end.
1: Data at the time of abnormal end is set in the area starting
from (S1)+11.
0001
H
0081
H
User
(S1)+1
Completion status
The status of when the instruction is ended is stored.
0: Normal
Values other than 0: Error (
System
(S1)+2
Channels used by
own station
Specify the channels to be used by the own station.
(
1 and 2
User
(S1)+3
Target station's
CPU type
Specify the CPU module on the station to be accessed.
0000
H
03D0
H
to 03D3
H
03E0
H
to 03E3
H
03FF
H
User
Set value
Description
0000
H
Control CPU (The access destination is the same as that
of when 03FF
H
is selected.)
03D0
H
Control system CPU (redundant CPU only)
03D1
H
Standby system CPU (redundant CPU only)
03D2
H
System A CPU (redundant CPU only)
03D3
H
System B CPU (redundant CPU only)
03E0
H
• Control CPU (single CPU system)
• CPU No.1 (multiple CPU system)
03E1
H
CPU No.2 (multiple CPU system)
03E2
H
CPU No.3 (multiple CPU system)
03E3
H
CPU No.4 (multiple CPU system)
03FF
H
Control CPU
When the instruction is executed by specifying a control system CPU
(03D0
H
) or standby system CPU (03D1
H
), if system switching occurs
in the target station, the instruction may fail (CPU module error code:
4244
H
, 4248
H
).
If the above error occurs and the instruction fails, execute the
instruction again.
(S1)+4
Target station's
network No.
Specify the network No. of the target station.
1 to 239: Network No.
254: Specify this when 254 is set for Jn.
1 to 239
254
User
(S1)+5
Target station
number
Specify the target station number.
Master station: 125 (7D
H
)
Master operating station: 126 (7E
H
) (only for modules supporting the
submaster function (
Local station, intelligent device station, submaster station: 1 to 120
When 125 (7D
H
) is set, the module always accesses the master
station (station number 0). When 126 (7E
H
) is set and the submaster
function is used, the module accesses the station operating as a
master operating station.
125 (7D
H
)
126 (7E
H
)
1 to 120
User
(S1)+6
Unused
0
User
b15
0
0
1
1
b7
b0
to
to