108
(Setting range)
*1
An interrupt occurs when the channel specified in "Channel No./Connection No." receives data.
5.
After the parameters are set, open the "Intelligent Function Module Interrupt Pointer Setting"
window.
Link the interrupt (SI) number assigned for the master/local module to the interrupt pointer of the CPU
module.
Project window
[Parameter]
[PLC Parameter]
[PLC System]
button
6.
Click the
button.
Device
Code
Device
No.
Detection Method
Interrupt
Condition
Word Device
Setting Value
Channel No./
Connection No.
Interrupt
(SI) No.
RX
0
H
to 3FFF
H
Level Detect and ON: Interrupt occurs by turning on
the device.
Level Detect and OFF: Interrupt occurs by turning off
the device.
Edge Detect and ON: Interrupt occurs at the rising
edge of the device.
Edge Detect and OFF: Interrupt occurs at the falling
edge of the device.
0 to 15
RY
0
H
to 3FFF
H
SB
0
H
to 1FF
H
RWr
0
H
to 1FFF
H
Level Detect and Equal: Interrupt occurs when
values match.
Level Detect and Unequal: Interrupt occurs when
values do not match.
Edge Detect and Equal: Interrupt occurs when
values match (first time only).
Edge Detect and Unequal: Interrupt occurs when
values do not match (first time only).
0 to 65535
(0
H
to FFFF
H
)
RWw
0
H
to 1FFF
H
SW
0
H
to 1FF
H
RECVS
Instruction
Edge Detect (fixed)
Scan Completed
(fixed)
*1
1 or 2
Item
Description
Setting range
PLC Side
Interrupt Pointer
Start No.
Enter the start number of an interrupt program (I
).
50 to 255 (Default: Blank)
Interrupt Pointer
Count
Enter the number of interrupt conditions.
1 to 16 (Default: Blank)
Intelligent
Module
Side
Start I/O No.
Enter the start I/O number of the master/local module.
0000
H
to 0FE0
H
(Default: Blank)
Start SI No.
Enter the start interrupt (SI) number of the master/local module.
0 to 15 (Default: Blank)