CHAPTER 7 PARAMETER SETTING
7
7.
5
R
e
fres
h P
a
ramet
e
rs
7.5
Refresh Parameters
Set link refresh ranges between the link devices of the master/local module and the devices of the CPU module.
(1) Setting procedure
1.
Set network setting parameters. (
2.
Open the setting window.
Project window
[Parameter]
[Network Parameter]
[Ethernet/CC IE/MELSECNET]
button
3.
Set parameters in the window.
4.
Click the
button.
Item
Description
Setting range
Assignment Method
Select a link device assignment method.
• Points/Start: Enter the points and start numbers of link devices.
• Start/End: Enter the start and end numbers of link devices.
• Points/Start
• Start/End
(Default: Start/End)
Transfer SB
Transfer
SW
Dev. Name
Set the link refresh ranges of SB and SW. One range can be set for
each SB and SW. (
(1) Transfer SB
• Link Side: Fixed at "SB".
• PLC Side: M, L, B, D, W, R, SB, ZR
(2) Transfer SW
• Link Side: Fixed at "SW".
• PLC Side: M, L, B, D, W, R, SW, ZR
(Default: Blank)
Points,
Start, End
• Link Side: 0 to 1FF
H
• PLC Side: Within device range of
CPU module
(Default: Blank)
Set bit devices in increments of 16
points and word devices in increments
of 4 points.
Ex.
0000
H
Device
name
(SB)
Transfer
SB
Transfer
SW
01FF
H
Master/local module
CPU module
0000
H
01FF
H
0000
H
01FF
H
0000
H
01FF
H
Device
name
(SW)
Device
name
(SB)
Device
name
(SW)