CHAPTER 11 PROGRAMMING
11
11.
4
U
sing Link
Sp
ecial Relay
(S
B)
and Link
Sp
ecial Regist
er
(SW
)
(Cyclic transmission restart)
8.
Specify the station to restart cyclic transmission in the following link special registers (SWs).
• Specifying a target station
Link stop/start direction (SW0000)
• Specifying a station number
Link stop/start direction (SW0001 to SW0008)
9.
Turn on System link start (SB0002).
10.
When the master/local module accepts the request, System link start request accept status
(SB0054) turns on.
11.
When cyclic transmission restart is completed, System link start completion status (SB0055) turns
on.
12.
If cyclic transmission is restarted with error, an error code will be stored in Data link start status
(entire system) (SW0052).
13.
Turn off System link start (SB0002).
Number
Description
Number
Description
SB0002
System link start
SW0000
Link stop/start direction
SB0003
System link stop
SW0001 to
SW0008
Link stop/start direction
SB0054
System link start request accept status
SW004A
Data link stop request station
SB0055
System link start completion status
SW0052
Data link start status (entire system)
SB0056
System link stop request accept status
SW0053
Data link stop status (entire system)
SB0057
System link stop completion status