CHAPTER 12 TROUBLESHOOTING
12
12.
5
E
rror
Code
List
D0A1
H
Transient data transmission
completion wait timeout
• Check if the cables and the switching hub are connected properly.
• Connect the cable to the other port on the module, and retry the operation.
• Reduce the frequency of transient transmission, and retry the operation.
• Execute hardware and self-loopback tests. If a failure occurs again, the
hardware of the master/local module may be faulty. Please consult your
local Mitsubishi representative.
D0A2
H
Transient data transmission
processing wait timeout
• Reduce the frequency of transient transmission, and retry the operation.
• Check if the switching hub and the cables at the request source are
connected properly.
D0A3
H
Transient data transmission error
• If the own station, target station, or relay station is disconnected from the
network, identify the cause of the disconnection and take action.
• Correct the number of the station for which transient data is to be sent,
and retry the operation.
• If the station for which transient data is to be sent is on another network,
check if the routing parameters for each station are correctly set.
D0A4
H
to D0A6
H
Transient transmission failed
• Check if the cables and the switching hub are connected properly.
• Connect the cable to the other port on the module, and retry the operation.
• Reduce the frequency of transient transmission, and retry the operation.
• Execute hardware and self-loopback tests. If a failure occurs again, the
hardware of the master/local module may be faulty. Please consult your
local Mitsubishi representative.
D0A7
H
Transient reception failed
• Check if the cables and the switching hub are connected properly.
• Connect the cable to the other port on the module, and retry the operation.
• Reduce the frequency of transient transmission, and retry the operation.
• Execute hardware and self-loopback tests. If a failure occurs again, the
hardware of the master/local module may be faulty. Please consult your
local Mitsubishi representative.
D0C0
H
Reserved station specification failed
(another process in progress)
Wait for a while, and reserve the station again.
D0C1
H
Reserved station cancellation failed
(another process in progress)
Wait for a while, and cancel the reserved station setting again.
D0C2
H
Data link stop failed (another process
in progress)
Wait for a while, and instruct the data link stop again.
D0C3
H
Data link start failed (another process
in progress)
Wait for a while, and instruct the data link start again.
D0C4
H
Temporary error invalid station setting
failed (another process in progress)
Wait for a while, and set the temporary error invalid station again.
D0C5
H
Temporary error invalid station
cancellation failed (another process in
progress)
Wait for a while, and cancel the temporary error invalid station setting again.
D0C6
H
Another station number setting change
failed (another process in progress)
Wait for a while, and set the station number of another station.
D0D0
H
Another station number setting failed
(another process in progress)
Wait for a while, and set the station number of another station.
D0E0
H
Station type mismatch
In the network configuration settings of the master station (submaster
station), change the station type to that of the own station.
D0E1
H
Own station reserved
• In the network configuration settings of the master station (submaster
station), cancel the reserved station setting.
• Change the station number of the own station to a station number that is
not reserved.
D0E2
H
Station No. already in use (own
station)
• Set a unique station number.
• After taking the above action, power off and on all the stations where this
error has been detected or reset them.
Error code
Error