417
CHAPTER 11 PROGRAMMING
11
11.
4
U
sing Link
Sp
ecial Relay
(S
B)
and Link
Sp
ecial Regist
er
(SW
)
(7) Checking test results before wiring
Test results are checked on the LEDs on the master/local module as well as using link special relays (SBs).
(
(a) Checking hardware test results
1.
When the hardware test is completed, Hardware test completion status (SB0090) is turned on.
2.
When failed, Hardware test normal/abnormal end (SB0091) is turned on.
(b) Checking self-loopback test results
1.
When the self-loopback test is completed, Self-loopback test completion status (SB0092) is turned
on.
2.
When failed, Self-loopback test normal/abnormal end (SB0093) is turned on.
(8) Checking test results after wiring
Test results are checked using the CC-Link IE Field Network diagnostics as well as link special relays (SBs).
(
(a) Checking loop test results
1.
When a loop test is started, Loop test request accept status (SB009A) is turned on.
2.
When the loop test is completed, Loop test completion status (SB0094) is turned on.
3.
When failed, Loop test normal/abnormal end (SB0095) is turned on.
Error details can be checked using Loop test result (SW0194). The station number where an error has
occurred in the loop test can be checked using Loop test error station (SW01A0 to SW01A7).
Number
Description
Number
Description
SB0090
Hardware test completion status
SB0091
Hardware test normal/abnormal end
Number
Description
Number
Description
SB0092
Self-loopback test completion status
SB0093
Self-loopback test normal/abnormal end
Number
Description
Number
Description
SB0094
Loop test completion status
SW0194
Loop test result
SB0095
Loop test normal/abnormal end
SW01A0 to
SW01A7
Loop test error station
SB009A
Loop test request accept status