285
CHAPTER 10 DEDICATED INSTRUCTIONS
10
10.
8
J
P
/G
P
.SEN
D (S
ending Da
ta
to
the
Pro
g
ramm
able Cont
roller
on A
n
ot
her
S
tat
io
n
)
(S1)+2
Channels used by
own station
Specify the channels to be used by the own station.
(
1 and 2
User
(S1)+3
Target station's
channel
Specify the channel of the target station where data is stored.
1 to 8 (channel
range available for
target station)
User
(S1)+4
Target station's
network No.
Specify the network No. of the target station.
1 to 239: Network No.
254: Specify this when 254 is set for Jn.
1 to 239
254
User
(S1)+5
Target station
number
Specify the target station number.
(1) Station number specification
Master station: 125 (7D
H
)
Master operating station: 126 (7E
H
) (only for modules
supporting the submaster function (
8))
Local station, intelligent device station, submaster station: 1 to
120
When 125 (7D
H
) is set, the module always accesses the master
station (station number 0). When 126 (7E
H
) is set and the
submaster function is used, the module accesses the station
operating as a master operating station.
To increase the reliability of data, it is recommended to execute
the instruction with the execution type in (S1)+0 set to "1: With
arrival confirmation".
(2) Group specification (The target station is on a network other
than CC-Link IE Field Network.)
81
H
to A0
H
: All stations in Group No.1 to No.32
(It can be set when the execution type set for (S1)+0 is "0:
Without arrival confirmation".)
(3) All stations specification
FF
H
: All stations on the target station's network No. (excluding
the own station)
(It can be set when the execution type set for (S1)+0 is "0:
Without arrival confirmation".)
When using the group specification or all stations specification
• The group specification cannot be used for CC-Link IE Field
Network stations.
• Writing of the data cannot be confirmed on the target station. For
whether data was written normally, check the device of the write
target station.
• Data cannot be written to the station with the station number
already in use or the station with no station number setting. Correct
the error then execute the instruction.
125 (7D
H
)
126 (7E
H
)
1 to 120
81
H
to A0
H
FF
H
User
(S1)+6
Unused
0
User
Device
Item
Setting data
Setting range
Set by
Group No.1: 81
H
Group No.2: 82
H
Group No.32: A0
H