448
D263
H
Constant link scan time setting error
(CCPASET)
• Correct the value in Constant link scan time (control data), and retry the
operation.
• If this error persists, please consult your local Mitsubishi representative.
D264
H
Station No. range error (CCPASET)
• Correct the value in the station No. (setting data) within 1 to 120, and retry
the operation.
• If this error persists, please consult your local Mitsubishi representative.
D265
H
Station No. already in use (CCPASET)
• Set a unique value in the station No. (setting data), and retry the
operation.
• If this error persists, please consult your local Mitsubishi representative.
D266
H
Slave station setting information error
(CCPASET)
• Correct the value in the slave station setting information (setting data),
and retry the operation.
• If this error persists, please consult your local Mitsubishi representative.
D267
H
Station type error (CCPASET)
• Correct the value in the station type (setting data), and retry the operation.
• If this error persists, please consult your local Mitsubishi representative.
D268
H
Device range assignment error
(CCPASET)
• Correct the value in the offset or the size of the link device in the slave
station(s) (setting data), and retry the operation.
• If this error persists, please consult your local Mitsubishi representative.
D269
H
Target station type error (REMFR/
REMTO)
Set the target station number specified using the REMFR or REMTO
instruction to the station number of the intelligent device station or remote
device station.
D26A
H
Target station No. error (REMFR/
REMTO)
Return the target station of the REMFR or REMTO instruction.
D26B
H
Network No. error (CCPASET
execution station)
Set any of 1 to 239 to Switch 1 (network No.) in the intelligent function
module switch setting of the master/local module.
D26C
H
Station No. error (CCPASET execution
station)
• To start the master/local module as a master station, set 0 to Switch 2 in
the intelligent function module switch setting.
• To start the master/local module as a local station, set Switch 2 in the
intelligent function module switch setting within 3101
H
to 3178
H
, and
31FF
H
.
• To start the master/local module as a submaster station, set Switch 2 in
the intelligent function module switch setting of the module within 4101
H
to
4178
H
.
• Check the serial number (first five digits) of the master/local module to
check if the module supports the function. If not, replace the module with
the one with the latest version.
D26D
H
Mode error (CCPASET execution
station)
Set 0 to Switch 3 in the intelligent function module switch setting of the
master/local module.
D26E
H
Operation setting error (CCPASET
execution station)
• To start the master/local module as a master station, set 0 or 2 for Switch
4 in the intelligent function module switch setting of the module.
• To start the master/local module as a local station, set 0 for Switch 4 in the
intelligent function module switch setting of the module.
• To start the master/local module as a submaster station, set 0 or 4 for
Switch 4 in the intelligent function module switch setting of the module.
• If this error persists, please consult your local Mitsubishi representative.
D26F
H
Submaster station No. error
(CCPASET execution station)
When executing the CCPASET instruction, set a submaster station number
in Slave station setting information (control data) within 1 to 120.
D270
H
Submaster station setting error
(CCPASET execution station)
When executing the CCPASET instruction, set one submaster station in the
station type in Slave station setting information (control data).
D271
H
Submaster station setting error
(CCPASET execution station)
When executing the CCPASET instruction, do not set a submaster station
number in Reserved station specification (control data).
D272
H
Submaster station setting error
(CCPASET execution station)
When executing the CCPASET instruction, do not set a submaster station
number in Error invalid station setting (control data).
Error code
Error
Action