286
(S1)+7
Number of
resends
During instruction execution
For the case where the instruction is not completed within the
monitoring time specified by (S1)+8, specify the number of
times the instruction is resent. (Valid when the execution type
set by (S1)+0 is "1: With arrival confirmation".)
0 to 15
User
When the instruction is completed
The number of resends performed (result) is stored. (Valid
when the execution type set by (S1)+0 is "1: With arrival
confirmation".)
System
(S1)+8
Arrival monitoring
time
Specify the monitoring time until instruction completion. (It can be set
when the execution type set by (S1)+0 is "1: With arrival
confirmation".)
If the instruction is not completed within the specified time, the
instruction is resent for the number of resends specified by (S1)+7.
0: 10 seconds
1 to 32767: 1 to 32767 seconds
0 to 32767
User
(S1)+9
Send data length
Specify the send data size of (S2) to (S2)+n.
1 to 960
To QnACPU:
1 to 480 words
User
(S1)+10
Unused
0
User
(S1)+11
Clock set flag
The valid or invalid status of data after (S1)+12 is stored.
(Data is stored when "1: Data at the time of abnormal end is set in
the area starting from (S1)+11." is set in the abnormal end type in
(S1)+0.) The stored data is not cleared even if the dedicated
instruction is normally completed.
0: Invalid
1: Valid
System
(S1)+12 to
(S1)+15
Clock data of
abnormal end
Clock data of abnormal end are stored in BCD format.
(Data is stored when "1: Data at the time of abnormal end is set in
the area starting from (S1)+11." is set in the abnormal end type in
(S1)+0.) The stored data is not cleared even if the dedicated
instruction is normally completed.
When the target station is QnACPU, 00
H
is stored in the year (the
first two digits of the year).
System
(S1)+16
Error-detected
station's network
No.*
1
The network No. of the station in which an error was detected is
stored.
(Data is stored when "1: Data at the time of abnormal end is set in
the area starting from (S1)+11." is set in the abnormal end type in
(S1)+0.) The stored data is not cleared even if the dedicated
instruction is normally completed.
1 to 239: Network No.
System
Device
Item
Setting data
Setting range
Set by
(S1)+12
(S1)+13
(S1)+14
(S1)+15
Month (01
H
to 12
H
)
Hour (00
H
to 23
H
)
Second (00
H
to 59
H
)
Day (01
H
to 31
H
)
Minute (00
H
to 59
H
)
00
H
(Sun.) to 06
H
(Sat.)
Day of week (00
H
to 06
H
)
Year (00
H
to 99
H
), first 2 digits
Year (00
H
to 99
H
), last 2 digits
b15
b8 b7
b0