9 - 89
MELSEC-Q
9 MAJOR POSITIONING CONTROL
POINT
•
The machine recognizes the presence of a movement amount change request when the data is
written to "
Cd.23
Speed-position switching control movement amount change register" with the
PLC program.
•
The new movement amount is validated after execution of the speed-position switching control (INC
mode), before the input of the speed-position switching signal.
•
The movement amount change can be enable/disable with the interlock function in position control
using the “speed-position switching latch flag” (
Md.31
Status : b1) of the axis monitor area.
Restrictions
(1) An axis error (error code: 516) will occur and the operation cannot start if
"continuous positioning control" or "continuous path control" is set in " Da.1
Operation pattern".
(2) "Speed-position switching control" cannot be set in " Da.2 Control system" of
the positioning data when "continuous path control" has been set in " Da.1
Operation pattern" of the immediately prior positioning data. (For example, if
the operation pattern of positioning data No. 1 is "continuous path control",
"speed-position switching control" cannot be set in positioning data No. 2.) An
axis error (error code: 516) will occur and the machine will carry out a
deceleration stop if this type of setting is carried out.
(3) An error (error code: 503) will occur if "current speed (-1)" is set in " Da.8
command speed".
(4) The software stroke limit range check during speed control is made only when
the following (a) and (b) are satisfied:
(a) "
Pr.21
Current feed value during speed control" is "1: Update current feed
value".
If the movement amount exceeds the software stroke limit range during
speed control in case of the setting of other than "1: Update current feed
value", an error (error code: 507 or 508) will occur as soon as speed control
is changed to position control and the axis will decelerate to a stop.
(b) When " Pr.1 Unit setting" is other than "2: degree"
If the unit is "degree", the software stroke limit range check is not performed.
(5) If the value set in "
Da.6
Positioning address/movement amount" is negative,
an error (error code: 530) will occur.
(6) Deceleration processing is carried out from the point where the speed-position
switching signal is input if the position control movement amount set in
" Da.6 Positioning address/movement amount" is smaller than the
deceleration distance from the " Da.8 Command speed".
(7) Turn ON the speed-position switching signal in the speed stabilization region
(constant speed status). A warning (warning code: 508) will occur because of
large deviation in the droop pulse amount if the signal is turned ON during
acceleration.
During use of the servo motor, the actual movement amount after switching of
speed control to position control is the "preset movement droop
pulse amount". If the signal is turned ON during acceleration/deceleration, the
stop position will vary due to large variation of the droop pulse amount. Even
though "
Md.29
Speed-position switching control positioning amount" is the
same, the stop position will change due to a change in droop pulse amount
when "
Da.8
Command speed" is different.
Summary of Contents for MELSEC-Q QD75M
Page 1: ...MELSEC Q QD75M Positioning Module User s Manual Details QD75M1 QD75M2 QD75M4 ...
Page 17: ...MEMO ...
Page 64: ...3 11 MELSEC Q 3 SPECIFICATIONS AND FUNCTIONS MEMO ...
Page 91: ...4 16 MELSEC Q 4 INSTALLATION WIRING AND MAINTENANCE OF THE PRODUCT MEMO ...
Page 108: ...5 17 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 112: ...5 21 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 116: ...5 25 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 138: ...5 47 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 182: ...5 91 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 188: ...5 97 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 194: ...5 103 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 253: ...5 162 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 274: ...6 21 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 275: ...6 22 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 276: ...6 23 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 277: ...6 24 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 278: ...6 25 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 279: ...6 26 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 280: ...6 27 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 281: ...6 28 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 282: ...6 29 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 283: ...6 30 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 284: ...6 31 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 285: ...6 32 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 286: ...6 33 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 287: ...6 34 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 288: ...6 35 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 289: ...6 36 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 290: ...6 37 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 291: ...6 38 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 292: ...6 39 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 293: ...6 40 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 294: ...6 41 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 295: ...6 42 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 296: ...6 43 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 297: ...6 44 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 298: ...6 45 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 299: ...6 46 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 300: ...6 47 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 301: ...6 48 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 302: ...6 49 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 303: ...6 50 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 304: ...6 51 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 305: ...6 52 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Page 332: ...7 7 MELSEC Q 7 MEMORY CONFIGURATION AND DATA PROCESS MEMO ...
Page 336: ...7 11 MELSEC Q 7 MEMORY CONFIGURATION AND DATA PROCESS MEMO ...
Page 347: ...MEMO ...
Page 477: ...9 116 MELSEC Q 9 MAJOR POSITIONING CONTROL MEMO ...
Page 539: ...11 36 MELSEC Q 11 MANUAL CONTROL MEMO ...
Page 663: ...14 18 MELSEC Q 14 DEDICATED INSTRUCTIONS MEMO ...
Page 771: ...Appendix 2 MELSEC Q APPENDICES MEMO ...
Page 845: ...Appendix 76 MELSEC Q APPENDICES MEMO ...
Page 855: ...Index 10 X X0 QD75 READY 3 15 X1 Synchronization flag 3 15 Z Zero speed Pr 130 5 74 ...