25. INVERTER CONNECTION
25.5 FREQROL Series Inverter Side Settings
25.5.9 Connecting to FREQROL-
A700 series
Communication settings
Make the communication settings of the inverter.
Be sure to perform the inverter reset after updating
each parameter.
(1) Communication port and corresponding parameters
(2) Communication settings of inverter
Set the following parameters using the PU (parameter
unit).
Do not change these parameters, even though they
can be monitored from the GOT. If they are changed,
communication with the GOT is disabled
*1
Setting items are parameter names described in the manual
of FREQROL-A700 series.
*2
Settings on the GOT can be changed.
When changing the settings on the GOT, be sure to change
the parameters on the inverter to correspond with the GOT
settings.
*3
Inverter default values (No need to change)
*4
Since the value has been set as a default, no setting is
required when the GOT is connected to the PU connector on
the inverter side.
HINT
HINT
HINT
(1) Automatic setting with Pr.999
If Pr.999 is set as the following, the communication
settings other than [PU communication station
number] and [Communication EEPROM write
selection] can be automatically set in a batch to
the default communication settings of the GOT
side.
*1
When the value of Pr.999 is monitored, 9999 is always
monitored.
(2) Inverters available for automatic batch setting
Parameters are not automatically set in a batch
depending on the SERIAL (production number)
symbol of the inverter to be used. For details,
contact your local distributor.
GOT connection
destination
Parameters corresponding to inverter
PU connector
Pr.79, Pr.117 to Pr.124, Pr.340, Pr.342
RS-485 terminal
Pr.79, Pr.331 to Pr.337, Pr.340 to Pr.342, Pr.549
Setting item
*1
Parameter No.
Set value
Settings
PU
connector
RS-485
terminal
PU communication
station number/RS-485
communication station
number
Pr.117
Pr.331
0 to 31
25.5.13 Station
number setting
PU communication
speed/RS-485
communication
speed
*2
Pr.118
Pr.332
192
*4
19200bps
PU communication
stop bit length*2
/
RS-485
communication stop bit
length
*2
Pr.119
Pr.333
10
Data length: 7bit
Stop bit length: 1bit
PU communication
parity check
/
RS-485
communication parity
check
*2
Pr.120
Pr.334
1
Odd
Number of PU
communication retries
/
Number of RS-485
communication retries
Pr.121
Pr.335
9999
The inverter will not
come to an alarm
stop.
PU communication
check time interval
/
RS-485
communication check
time interval
Pr.122
Pr.336
9999
*4
Communication check
suspension
PU communication
wait time setting
/
RS-485
communication wait
time setting
Pr.123
Pr.337
0
0ms
PU communication CR/
LF selection
/
RS-485
communication CR/LF
selection
Pr.124
Pr.341
1
*3
With CR, without LF
Protocol selection
-
Pr.549
0
*3
Mitsubishi inverter
protocol
Operation mode
selection
Pr.79
PU
Connector
1
PU operation mode
RS-485
0
*3
External operation
mode at power on
Communication startup
mode selection
Pr.340
PU
Connector
0
*3
Refer to Pr.79
settings.
RS-485
1
Network operation
mode
Communication
EEPROM write
selection
Pr.342
0
*3
Written to RAM and
EEPROM
Parameter
No.
Set
value
Description
Operation in parameter setting
mode
Pr.999
*1
10
GOT initial settings
(PU connector)
[AUTO]
[GOT]
[1]
Write
11
GOT initial settings
(RS-485 terminal)
-
Setting item
*1
Parameter No.
Set value
Settings
PU
connector
RS-485
terminal
Summary of Contents for GT14
Page 1: ......
Page 2: ......
Page 34: ...A 32 ...
Page 46: ...1 4 1 OVERVIEW 1 1 Features ...
Page 60: ...3 6 3 SPECIFICATIONS 3 4 Battery specifications ...
Page 72: ...5 8 5 UL cUL STANDARDS AND EMC DIRECTIVE 5 2 EMC Directive ...
Page 108: ...6 36 6 OPTION 6 7 With wall mounting Attachment ...
Page 124: ...8 10 8 COMMUNICATION CABLE 8 2 External Cable Relay Cable ...
Page 172: ...11 16 11 COMMUNICATION INTERFACE SETTING COMMUNICATION SETTING 11 3 Ethernet Setting ...
Page 200: ...12 28 12 DISPLAY AND OPERATION SETTINGS GOT SET UP 12 6 License Management ...
Page 296: ...14 92 14 FILE DISPLAY AND COPY PROGRAM DATA CONTROL 14 2 Various Data Control ...
Page 320: ...15 24 15 GOT SELF CHECK DEBUG AND SELF CHECK 15 4 GOT start time ...
Page 322: ...16 2 16 CLEANING DISPLAY SECTION CLEAN ...
Page 336: ...17 14 17 INSTALLATION OF COREOS BOOTOS AND STANDARD MONITOR OS 17 5 CoreOS ...
Page 360: ...19 8 19 MAINTENANCE AND INSPECTION 19 5 Backlight Shutoff Detection ...
Page 382: ......
Page 450: ...22 34 22 COMPUTER LINK CONNECTION 22 6 Precautions ...
Page 508: ...23 58 23 ETHERNET CONNECTION 23 5 Precautions ...
Page 526: ......
Page 592: ...26 22 26 SERVO AMPLIFIER CONNECTION 26 7 Precautions ...
Page 598: ...27 6 27 ROBOT CONTROLLER CONNECTION 27 6 Precautions ...
Page 607: ...MULTIPLE GOT CONNECTION FUNCTION 29 MULTIPLE GOT CONNECTION FUNCTION 29 1 ...
Page 608: ......
Page 619: ...MULTI CHANNEL FUNCTION 30 MULTI CHANNEL FUNCTION 30 1 ...
Page 620: ......
Page 635: ...FA TRANSPARENT FUNCTION 31 FA TRANSPARENT FUNCTION 31 1 ...
Page 636: ......
Page 688: ...31 52 31 FA TRANSPARENT FUNCTION 31 7 Precautions ...
Page 698: ...App 10 APPENDICES Appendix 2 Usage Condition of Utility Function ...
Page 703: ......
Page 704: ......
Page 705: ......
Page 706: ......
Page 738: ...A 32 ...
Page 748: ......
Page 820: ...33 44 33 CONNECTION TO OMRON PLC 33 4 Device Range that Can Be Set ...
Page 834: ...34 14 34 CONNECTION TO OMRON TEMPERATURE CONTROLLER 34 7 Precautions ...
Page 912: ...37 22 37 CONNECTION TO JTEKT PLC 37 7 Precautions ...
Page 930: ...38 18 38 CONNECTION TO SHARP PLC 38 6 Device Range that Can Be Set ...
Page 980: ...41 16 41 CONNECTION TO TOSHIBA PLC 41 4 Device Range that Can Be Set ...
Page 996: ...43 8 43 CONNECTION TO PANASONIC SERVO AMPLIFIER 43 7 Precautions ...
Page 1052: ...46 10 46 CONNECTION TO HITACHI PLC 46 6 Device Range that Can Be Set ...
Page 1092: ...47 40 47 CONNECTION TO FUJI PLC 47 5 Precautions ...
Page 1108: ...48 16 48 CONNECTION TO FUJI TEMPERATURE CONTROLLER 48 7 Precautions ...
Page 1142: ...49 34 49 CONNECTION TO YASKAWA PLC 49 4 Device Range that Can Be Set ...
Page 1332: ...55 28 55 CONNECTION TO GE PLC 55 7 Precautions ...
Page 1348: ...56 16 56 CONNECTION TO LS INDUSTRIAL SYSTEMS PLC 56 6 Device Range that Can Be Set ...
Page 1352: ...57 4 57 CONNECTION TO SICK SAFETY CONTROLLER 57 5 Device Range that Can Be Set ...
Page 1368: ...58 16 58 CONNECTION TO SIEMENS PLC 58 4 Device Range that Can Be Set ...
Page 1370: ...59 2 59 CONNECTION TO HIRATA CORPORATION HNC CONTROLLER ...
Page 1372: ...60 2 60 CONNECTION TO MURATEC CONTROLLER ...
Page 1374: ......
Page 1515: ...MODBUS CONNECTIONS 63 MODBUS R RTU CONNECTION 63 1 64 MODBUS R TCP CONNECTION 64 1 ...
Page 1516: ......
Page 1537: ...CONNECTIONS TO PERIPHERAL EQUIPMENT 65 VNC R SERVER CONNECTION 65 1 ...
Page 1538: ......
Page 1545: ......
Page 1546: ......