Measurements on the main circuit
Maintenance and inspection
8 - 18
Use an FFT to measure the output voltage accurately. A tester or general measuring
instrument cannot measure accurately.
When the carrier frequency exceeds 5 kHz, do not use this instrument since using it may
increase eddy-current losses produced in metal parts inside the instrument, leading to
burnout. If the wiring length between the inverter and motor is long, the instrument and CT
may generate heat due to line-to-line leakage current.
When the setting of Pr. 195 "ABC1 terminal function selection" is positive logic.
Item
Measuring Point
Measuring
Instrument
Remarks (Reference Measurement Value)
Frequency
setting signal
Across 2, 4 (positive)
and 5
Moving-coil type
(Tester and such
may be used)
(Internal resist-
ance: 50k
Ω
or
larger)
0–10 V DC, 4–20 mA
"5" is
common
Across 1 (positive)
and 5
0–
±
5 V DC, 0–
±
10 V DC
Frequency set-
ting power
supply
Across 10 (positive)
and 5
5.2 V DC
Across 10E (positive)
and 5
10 V DC
Frequency
meter signal
Across CA (positive)
and 5
About 20mA at maximum frequency
Across AM (positive)
and 5
Approximately 10V DC at maximum
frequency (without frequency meter)
Start signal
Select signal
Across STF,
STR, RH, RM, RL,
JOG, RT, AU, STOP,
CS and SD (0V)
When open: 20 to 30 V DC
ON voltage: 1 V or less
"SD" is
common
(source
logic)
Reset
Across RES-SD
(0V)
Output stop
Across MRS-SD
(0V)
Alarm signal
Across A1-C1 and
B1-C1
Moving-coil type
(such as tester)
Continuity check
Normal
Abnormal
Across A1-C1
Discontinuity
Continuity
Across B1-C1
Continuity
Discontinuity
Tab. 8-7:
Measuring Points and Instruments (2)
Summary of Contents for FR-A700 EC
Page 2: ......
Page 4: ......
Page 24: ...Description of the Case Product Checking and Part Identification 1 4 ...
Page 38: ...Enclosure design Installation 2 14 ...
Page 774: ...Specifications FR A 740 01800 to 12120 Appendix A 4 ...
Page 820: ...Parameter list with instruction codes Appendix A 50 ...
Page 825: ......