Troubleshooting
Reset method of protective function
FR-A700 EC
7 - 23
7.3
Reset method of protective function
Eliminate the cause of the error befor you reset the inverter. Note that the internal thermal in-
tegrated value of the electronic thermal relay function and the number of retries are cleared
(erased) by resetting the inverter. It takes about 1s for reset.
The inverter can be reset by performing any of the following operations:
●
Using the operation panel, press the STOP/RESET key to reset the inverter.
(Enabled only when the inverter protective function is activated (major fault). (Refer to
page 7-11 for major fault.))
●
Switch power off once, then switch it on again.
●
Turn on the reset signal RES for more than 0.1s. (Connect the terminals RES and SD when
using sink logic or terminals RES and PC as shown Fig. 7-3 when using source logic).
(If the RES signal is kept on, "Err." appears (flickers) to indicate that the inverter is in are
set status.)
Fig. 7-1:
Resetting the inverter by using the operation
panel
I001296E
Fig. 7-2:
Resetting the inverter by switching the power
supply off an on
I001297E
Fig. 7-3:
Resetting the inverter by turning on the RES
signal
I000249C
NOTE
For the 02160 or more, you can set Pr. 75 to disable reset operation until the thermal cumu-
lative amount reaches 0 when a thermal trip (THM, THT) or an overcurrent trip (OC1 to OC3)
occurs consecutively twice.
RESET
RES
PC
Inverter
Summary of Contents for FR-A700 EC
Page 2: ......
Page 4: ......
Page 24: ...Description of the Case Product Checking and Part Identification 1 4 ...
Page 38: ...Enclosure design Installation 2 14 ...
Page 774: ...Specifications FR A 740 01800 to 12120 Appendix A 4 ...
Page 820: ...Parameter list with instruction codes Appendix A 50 ...
Page 825: ......