Parameter
Selection and protection of a motor
FR-A700 EC
6 - 235
Tune second applied motor
●
When you want to switch two motors with one inverter, set the second motor in Pr. 450
"Second applied motor" (refer to section 6.12.2). Initial setting is without second applied
motor.
●
Turning the RT signal on makes the following parameters for the second parameters valid.
Function
RT Signal ON
(second motor)
RT Signal OFF
(first motor)
Motor capacity
Pr. 453
Pr. 80
Number of motor poles
Pr. 454
Pr. 81
Motor excitation current
Pr. 455
Pr. 82
Motor rated voltage
Pr. 456
Pr. 83
Rated motor frequency
Pr. 457
Pr. 84
Motor constant (R1)
Pr. 458
Pr. 90
Motor constant (R2)
Pr. 459
Pr. 91
Motor constant (L1)
Pr. 460
Pr. 92
Motor constant (L2)
Pr. 461
Pr. 93
Motor constant (X)
Pr. 462
Pr. 94
Auto tuning setting/status
Pr. 463
Pr. 96
Tab. 6-61:
Validation of parameters by the RT signal
NOTES
The RT signal is assigned to the terminal RT in the initial setting. By setting "3" in any of Pr.
178 to Pr. 189 (input terminal function selection), you can assign the RT signal to the other
terminal.
Changing the terminal assignment using Pr. 178 to Pr. 189 "Input terminal function
selection" may affect other functions. Make setting after confirming the function of each
terminal.
Summary of Contents for FR-A700 EC
Page 2: ......
Page 4: ......
Page 24: ...Description of the Case Product Checking and Part Identification 1 4 ...
Page 38: ...Enclosure design Installation 2 14 ...
Page 774: ...Specifications FR A 740 01800 to 12120 Appendix A 4 ...
Page 820: ...Parameter list with instruction codes Appendix A 50 ...
Page 825: ......