Inspection
Maintenance and inspection
8 - 4
8.1.4
Display of the life of the inverter parts
The self-diagnostic alarm is output when the life span of the control circuit capacitor, cooling fan,
each parts of the inrush current limit circuit is near to give an indication of replacement time. For
the life check of the main circuit capacitor, the alarm signal (Y90) will not be output if a measuring
method of is not performed. (Refer to the description below.)
The life alarm output can be used as a guideline for life judgement.
Display of the life alarm
Pr. 255 "Life alarm status display" can be used to confirm that the control circuit capacitor, main
circuit capacitor, cooling fan, and each parts of the inrush current limit circuit has reached the life
alarm output level.
Read the setting of parameter 255.
When the life alarm output level is reached, the bits are set as follows.
Parts
Judgement Level
Main circuit capacitor
85% of the initial capacity
Control circuit capacitor
Estimated 10% life remaining
Inrush current limit circuit
Estimated 10% life remaining (Power on: 100,000 times left)
Cooling fan
Less than 40% of the predetermined speed
Tab. 8-2:
Guideline for the alarm signal output
I001262E
Fig. 8-1:
Read parameter 255
I001261E
Fig. 8-2:
Bits of parameter 255
Call up Pr. 255
Read the setting of Pr. 255
The bit image is displayed
in decimal.
Control circuit capacitor life
Main circuit capacitor life
Cooling fan life
Inrush current limit circuit life
Summary of Contents for FR-A700 EC
Page 2: ......
Page 4: ......
Page 24: ...Description of the Case Product Checking and Part Identification 1 4 ...
Page 38: ...Enclosure design Installation 2 14 ...
Page 774: ...Specifications FR A 740 01800 to 12120 Appendix A 4 ...
Page 820: ...Parameter list with instruction codes Appendix A 50 ...
Page 825: ......