Simple mode parameter list
Basic settings
5 - 2
Pr.
Name
Incre-
ments
Initial
value
Range
Description
Refer
to
7
Acceleration time
0.1s
5/15s
0–3600s
Acceleration/deceleration time
can be set.
Initial values differ according to
the inverter capacity.
(00250 or less/00310 or more)
8
Deceleration time
0.1s
10/30s
0–3600s
9
Electronic thermal O/L
relay
0.01/
0.1A
Rated
inverter
output
current
0–500/
0–3600A
Protect the motor from overheat
by the inverter.
Set the rated motor current.
The increments and setting
range differ according to
the inverter capacity.
(01800 or less/02160 or more)
79
Operation mode
selection
1
0
0/1/2/3/4/6/7
Select the start command location
and frequency command location.
125
Terminal 2 frequency
setting gain frequency
0.01Hz
50Hz
0–400Hz
Frequency for the maximum value
of the potentiometer (5V initial
value) can be changed.
126
Terminal 4 frequency
setting gain frequency
0.01Hz
50Hz
0–400Hz
Frequency for the maximum cur-
rent input (20mA initial value) can
be changed.
160
User group read
selection
1
9999
0/1/9999
Make extended parameters valid
Tab. 5-2:
Simple mode parameters (2)
Summary of Contents for FR-A700 EC