Parameter overview
Parameter
6 - 62
Func-
tion
Parameter
Name
Incre-
ments
Initial
Value
Setting
Range
Description
Para-
meter
copy
Para-
meter
clear
All
para-
meter
clear
Refer
to
page
Re
la
te
d
parameters
✔
: enabled
—: disabled
Free parameter
888
Free parameter 1
1
9999
0–9999
Parameters you can use for your
own purposes
Used for maintenance, manage-
ment, etc. by setting a unique
number to each inverter when
multiple inverters are used.
✔
—
—
889
Free parameter 2
1
9999
0–9999
✔
—
—
Energy saving monitor
891
Refer to Pr. 52
892
Load factor
0.1%
100%
30–150%
Set the load factor for commercial
power-supply operation. This
value is used to calculate the
power consumption estimated
value during commercial power
supply operation.
✔
✔
✔
893
Energy saving monitor
reference (motor
capacity)
0.01/
0.1kW *
SLD/LD/
ND/HD
value of
Applied
motor
Capacity
0.1–55/
0–3600kW *
Set the motor capacity (pump
capacity).
Set when calculating power sav-
ings rate and average power sav-
ings rate value.
* The setting depends on the
inverter capacity:
(01800 or less/02160 or more)
✔
✔
✔
894
Control selection
during commercial
power-supply
operation
1
0
0
Discharge damper control (fan)
✔
✔
✔
1
Inlet damper control (fan)
2
Valve control (pump)
3
Commercial power-supply drive
(fixed value)
895
Power saving rate
reference value
1
9999
0
Consider the value during com-
mercial power-supply operation as
100%.
✔
✔
✔
1
Consider the Pr. 893 setting as
100%.
9999
No function
896
Power unit cost
0.01
9999
0–500
Set the power unit cost. Display
the power savings rate on the
energy saving monitor
✔
✔
✔
9999
No function
897
Power saving monitor
average time
1
9999
0
Average for 30 minutes
✔
✔
✔
1–1000h
Average for the set time
9999
No function
898
Power saving
cumulative monitor
clear
1
9999
0
Cumulative monitor value clear
✔
✔
✔
1
Cumulative monitor value hold
10
Cumulative monitor continue
(communication data upper limit
9999)
9999
Cumulative monitor continue
(communication data upper limit
65535)
899
Operation time rate
(estimated value)
0.1%
9999
0–100%
Use for calculation of annual
power saving amount. Set the
annual operation ratio (consider
365 days
×
24hr as 100%).
✔
✔
✔
9999
No function
Tab. 6-1:
Parameter overview (62)
Summary of Contents for FR-A700 EC
Page 2: ......
Page 4: ......
Page 24: ...Description of the Case Product Checking and Part Identification 1 4 ...
Page 38: ...Enclosure design Installation 2 14 ...
Page 774: ...Specifications FR A 740 01800 to 12120 Appendix A 4 ...
Page 820: ...Parameter list with instruction codes Appendix A 50 ...
Page 825: ......