Energy saving operation and energy saving monitor
Parameter
6 - 360
6.18.2
Energy saving monitor (Pr. 891 to Pr. 899)
From the power consumption estimated value during commercial power supply operation, the
energy saving effect by use of the inverter can be monitored/output.
The above parameters allow its setting to be changed during operation in any operation mode
even if "0" (initial value) is set in Pr. 77 "Parameter write selection".
Pr.
No.
Name
Initial
Value
Setting Range
Description
Parameters referred to
Refer to
Section
52
DU/PU main display
data selection
0
(Output
frequency)
0/5–14/17–20/
22–25/32–35/
50–57/100
50: Power saving monitor
51: Cumulative saving power
monitor
3
52
54
158
Base frequency
DU/PU main
display data
selection
CA terminal func-
tion selection
AM terminal func-
tion selection
54
CA terminal function
selection
1
(Output
frequency)
1–3/5–14/17/18/
21/24/32–34/50/
52/53/70
50: Power saving monitor
158
AM terminal
function selection
891
Cumulative power
monitor digit shifted
times
9999
0–4
Set the number of times to shift the
cumulative power monitor digit.
Clamp the monitoring value at max-
imum.
9999
No shift
Clear the monitor value when it
exceeds the maximum value.
892
Load factor
100%
30–150%
Set the load factor for commercial
power-supply operation.
Multiplied by the power consump-
tion rate (page 6-365) during com-
mercial power supply operation.
893
Energy saving
monitor reference
(motor capacity)
Applied
motor
Capacity
01800
or
less
0.1–55kW Set the motor capacity (pump
capacity).
Set when calculating power saving
rate, average power saving rate
value, commercial operation power.
02160
or
more
0–3600W
894
Control selection
during commercial
power-supply
operation
0
0
Discharge damper control (fan)
1
Inlet damper control (fan)
2
Valve control (pump)
3
Commercial power-supply drive
(fixed value)
895
Power saving rate
reference value
9999
0
Consider the value during commer-
cial power-supply operation as
100%
1
Consider the Pr. 893 setting as
100%.
9999
No function
896
Power unit cost
9999
0–500
Set the power unit cost. Display the
power saving amount charge on the
energy saving monitor.
9999
No function
897
Power saving
monitor average time
9999
0
Average for 30 minutes
1–1000h
Average for the set time
9999
No function
898
Power saving
cumulative monitor
clear
9999
0
Cumulative monitor value clear
1
Cumulative monitor value hold
10
Totalization continued
(communication data upper limit:
9999)
9999
Totalization continued
(communication data upper limit:
65535)
899
Operation time rate
(estimated value)
9999
0–100%
Use for calculation of annual power
saving amount.
Set the annual operation ratio (con-
sider 365 days × 24hr as 100%).
9999
No function
Summary of Contents for FR-A700 EC
Page 2: ......
Page 4: ......
Page 24: ...Description of the Case Product Checking and Part Identification 1 4 ...
Page 38: ...Enclosure design Installation 2 14 ...
Page 774: ...Specifications FR A 740 01800 to 12120 Appendix A 4 ...
Page 820: ...Parameter list with instruction codes Appendix A 50 ...
Page 825: ......