Parameter
Communication operation and setting
FR-A700 EC
6 - 487
6.23.8
USB communication (Pr. 547, Pr. 548)
Inverter setup can be easily performed using the FR Configurator by connecting the inverter and
personal computer with a USB cable.
When using USB communication, set "3" in Pr. 551 "PU mode operation command source
selection."
You can perform parameter setting and monitoring with the FR Configurator. Refer to the
instruction manual of the FR-Configurator for details.
Pr. No.
Name
Initial
Value
Setting
Range
Description
Parameters referred to
Refer to
Section
547
USB communication
station number
0
0 to 31
Inverter station number specification
551
PU mode operation
command source
selection
548
USB communication
check time interval
9999
0
USB communication is enabled. How-
ever, the inverter will come to an alarm
stop (E. USB) if operation is changed to
PU operation mode.
0.1 to 999.8s
Sets the interval of communication
check time.
If a no-communication state persists for
longer than the permissible time, the
inverter will come to trip (E.USB).
9999
No communication check
Specification
Description
Interface
Conforms to USB1.1
Transmission speed
12Mbps
Wiring Length
5m
Connector
USB mini B connector (receptacle mini B type)
Power supply
Self-power supply
Tab. 6-167:
USB communication specifications
I001460E
Fig. 6-234:
Connection to the USB interface
Removal of cover
Place a flat-blade screwdriver, etc. in a
slot and push up the cover to open.
USB cable
USB connector
Summary of Contents for FR-A700 EC
Page 2: ......
Page 4: ......
Page 24: ...Description of the Case Product Checking and Part Identification 1 4 ...
Page 38: ...Enclosure design Installation 2 14 ...
Page 774: ...Specifications FR A 740 01800 to 12120 Appendix A 4 ...
Page 820: ...Parameter list with instruction codes Appendix A 50 ...
Page 825: ......