Selection of operation mode and operation location
Parameter
6 - 436
Switching of command source by external terminal (X67)
In network operation mode, the command source switching signal (X67) can be used to switch
the operation command source and speed command source. This signal can be utilized to con-
trol the signal input from both the external terminal and communication.
Set "67" to any of Pr. 178 to Pr. 189 to assign the X67 signal to the external terminal.
When the X67 signal is off, the operation command source and speed command source are
external.
X67 Signal State
Operation Command Source
Speed Command Source
No signal assignment
According to Pr. 338
According to Pr. 339
ON
OFF
Operation is valid only from external terminal signal.
Tab. 6-129:
Switching of command source by the signal X67
NOTES
The ON/OFF state of the X67 signal is reflected only during a stop. It is reflected after a stop
when the terminal is switched during operation.
When the X67 signal is off, a reset via communication is disabled.
Changing the terminal assignment using Pr. 178 to Pr. 189 "Input terminal function selec-
tion" may affect the other functions. Please make setting after confirming the function of
each terminal.
Summary of Contents for FR-A700 EC
Page 2: ......
Page 4: ......
Page 24: ...Description of the Case Product Checking and Part Identification 1 4 ...
Page 38: ...Enclosure design Installation 2 14 ...
Page 774: ...Specifications FR A 740 01800 to 12120 Appendix A 4 ...
Page 820: ...Parameter list with instruction codes Appendix A 50 ...
Page 825: ......