Motor brake and stop operation
Parameter
6 - 262
The input signal terminal used differs according to the Pr. 178 to Pr. 189 settings.
The output signal terminal used differs according to the Pr. 190 to Pr. 196 settings.
The current should be within the permissible current of the transistor in the inverter.
(24V/ 0.1A DC)
I001570E
Fig. 6-110:
Connection example with mechanical brake (Pr. 184 = 15, Pr. 190 = 20)
NOTES
When brake sequence mode is selected, automatic restart after instantaneous power failure
is invalid.
When using this function, set the acceleration time to 1s or longer.
Changing the terminal function using any of Pr. 178 to Pr. 186 and Pr. 190 to Pr. 196 may
affect the other functions. Make setting after confirming the function of each terminal.
Start signal
Multi-speed signal
BRI signal
Mechanical
brake
Motor
Power
supply
BOF signal: Brake opening request signal
BRI signal: Brake opening completion signal
BOF signal
24V DC
MC
MC