Function assignment of external terminals
Parameter
6 - 286
6.14
Function assignment of external terminals
6.14.1
Input terminal function selection (Pr. 178 to Pr. 189)
Use these parameters to select/change the input terminal functions.
Purpose
Parameters that must be set
Refer to
Section
Assign function to input terminal
Input terminal function selection
Pr. 178–Pr. 189
Set MRS signal (output shutoff) to nor-
mally closed contact specification
MRS input selection
Pr. 17
Make the second function valid only
during constant speed operation
RT reflection time selection
Pr. 155
Assign start signal and forward/
reverse command to other signals
Start signal (STF/STF) operation selection
Pr. 250
Assign function to output terminal
Output terminal function selection
Pr. 190–Pr. 196
Detect output frequency
Up-to-frequency sensitivity
Output frequency detection
Pr. 41–Pr. 43,
Pr. 50, Pr. 116,
Pr. 865
Detect output current
Output current detection
Zero current detection
Pr. 150–Pr. 153,
Pr. 166, Pr. 167
Remote output function
Remote output
Pr. 495–Pr. 497
Detect output torque
Output torque detection
Pr. 864
Pr.
No.
Name
Initial
Value
Initial Signal
Setting Range
Parameters referred to
Refer to
Section
178
STF terminal
function selection
60
STF (forward rotation
command)
0–20/22–28/37/42–
44/50/60/62/64–71/
9999
—
179
STR terminal
function selection
61
STR (reverse rotation
command)
0–20/22–28/37/42–
44/50/61/62/64–71/
9999
180
RL terminal
function selection
0
RL (low-speed operation
command)
0–20/22–28/37/42–
44/50/62/64–71/9999
181
RM terminal
function selection
1
RM (middle-speed operation
command)
182
RH terminal
function selection
2
RH (high speed operation
command)
183
RT terminal
function selection
3
RT (second function selection)
184
AU terminal
function selection
4
AU (terminal 4 input selection)
0–20/22–28/37/42–
44/50/62–71/9999
185
JOG terminal
function selection
5
JOG (Jog operation selection)
0–20/22–28/37/42–
44/50/62/64–71/9999
186
CS terminal
function selection
6
CS (selection of automatic
restart after instantaneous
power failure)
187
MRS terminal
function selection
24
MRS (output stop)
188
STOP terminal
function selection
25
STOP (start self-holding
selection)
189
RES terminal
function selection
62
RES (inverter reset)
Summary of Contents for FR-A700 EC
Page 2: ......
Page 4: ......
Page 24: ...Description of the Case Product Checking and Part Identification 1 4 ...
Page 38: ...Enclosure design Installation 2 14 ...
Page 774: ...Specifications FR A 740 01800 to 12120 Appendix A 4 ...
Page 820: ...Parameter list with instruction codes Appendix A 50 ...
Page 825: ......