Parameter
Frequency setting by external terminals
FR-A700 EC
6 - 187
Fig. 6-69:
Jog operation signal timing chart
I001324C
I001129E
Fig. 6-70:
Jog operation in the external operation mode
Hz
t
t
t
STF
STR
Pr. 15
Pr. 16
Pr. 20
t
JOG
Input signals
Jog
frequency
Forward rotation
Output frequency
Reverse
rotation
ON
ON
ON
Screen at powering on
Confirm that the external operation mode is
selected. (EXT indication is lit)
If not displayed, press the PU/EXT key to change
to the external operation mode If the operation
mode still does not change, set Pr. 79 to change
to the external operation mode.
Turn the JOG switch on.
Turn the start switch STF or STR on.
The motor rotates while the start switch is ON.
It rotates at 5Hz (initial value of Pr. 15).
Turn the start switch STF or STR off.
Forward
rotation
Reverse
rotation
Reverse
rotation
Forward
rotation
ON
ON
OFF
Stop
Rotates while ON.
Operation
Display
Summary of Contents for FR-A700 EC
Page 2: ......
Page 4: ......
Page 24: ...Description of the Case Product Checking and Part Identification 1 4 ...
Page 38: ...Enclosure design Installation 2 14 ...
Page 774: ...Specifications FR A 740 01800 to 12120 Appendix A 4 ...
Page 820: ...Parameter list with instruction codes Appendix A 50 ...
Page 825: ......