Wiring
Main circuit connection
FR-A700 EC
3 - 15
Total wiring lenght
The maximum possible length of the motor cables depends on the capacity of the inverter and
the selected carrier frequency. The cables should never be longer than 100m (unshielded).
The lengths in the following table are for unshielded cables. When shielded cables are use di-
vide the values listed in the table by 2. Note that the values are for the total wiring length – if you
connect more than one motor in parallel you must add the lengths of the individual motor cables.
Pr. 72 "PWM frequency selection" setting (carrier frequency)
00023
00038
≥
00052
≤
2 (2kHz)
300m
500m
500m
3 (3kHz), 4 (4kHz)
200m
300m
500m
5 (5kHz) to 9 (9kHz)
100m
≥
10 (10kHz)
50m
Tab. 3-5:
Total wiring lenght
NOTE
For the 02160 or more, the setting range of Pr. 72 PWM frequency selection is "0 to 6".
Fig. 3-7:
Total wiring lenght (00052 or more)
I001017E
NOTE
Note that the motor windings are subjected to significantly higher loads when the motor is
operated by inverter than with normal mains operation. The motors must be approved for
inverter operation by the manufacturer (refer also to section 3.9.5).
≤
500m
300m
300m
300m + 300m = 600m