Monitor display and monitor output signals
Parameter
6 - 336
How to calibrate the terminal CA when using the operation panel FR-DU07
The following example shows how to calibrate the maximum value of the CA terminal to the
60Hz output frequency. This operation is performed in PU mode.
I001599E
Fig. 6-154:
CA terminal calibration
NOTES
Calibration can also be made for external operation. Set the frequency in external operation
mode, and make calibration in the above procedure.
Calibration can be made even during operation.
For the operation procedure using the parameter unit (FR-PU04, FR-PU07), refer to the
parameter unit instruction manual.
Confirmation of the RUN indication and
operation mode indication
Press the MODE key to choose the parameter
setting mode.
Turn the digital dial until "C..." appears.
Press set to display "C---".
Turn the digital dial until „C 0“ appears.
Set to C0 „CA terminal calibration“.
Press the SET key to enable setting.
If the inverter is at a stop, press the FWD or REV
key to start the inverter.
(Motor needs not be connected.)
Wait until the output frequency of 50Hz is reached.
Turn the digital dial to adjust the indicator needle
to the desired position.
(In contrast to the output analog current the value
shown for C0 does not change when turning the
digital dial.)
Press the SET key to set. Setting is complete.
(When Pr. 54 = 1)
Operation
Display
The parameter number
read previously appears.
C0 to C41 setting is
enabled.
The monitor set to
Pr. 54 "CA terminal
function selection" is
displayed.
Analog indicator
Flicker ... Parameter setting complete!
앫
By turning the digital dial, you can read another parameter.
앫
Press the SET key to return to the "C---" indication (step
).
앫
Press the SET key twice to show the next parameter (Pr.CL).
Summary of Contents for FR-A700 EC
Page 2: ......
Page 4: ......
Page 24: ...Description of the Case Product Checking and Part Identification 1 4 ...
Page 38: ...Enclosure design Installation 2 14 ...
Page 774: ...Specifications FR A 740 01800 to 12120 Appendix A 4 ...
Page 820: ...Parameter list with instruction codes Appendix A 50 ...
Page 825: ......