Maintenance and inspection
Measurements on the main circuit
FR-A700 EC
8 - 17
Measuring Points and Instruments
Item
Measuring Point
Measuring
Instrument
Remarks (Reference Measurement Value)
Power supply
voltage U1
Across R/L1-S/L2,
S/L2-T/L3, T/L3-R/L1
Moving-iron type
AC voltmeter
Commercial power supply
Within permissible AC voltage fluctuation
(Refer to appendix A)
Power supply
side current I1
R/L1, S/L2, and T/L3
line currents
Moving-iron type
AC ammeter
Power supply
side power P1
R/L1, S/L2, T/L3
and R/L1-S/L2, S/L2-
T/L3, T/L3-R/L1
Electrodynamic
type single-phase
wattmeter
P1 = W11 + W12 + W13 (3-wattmeter method)
Power supply
side power
factor Pf1
Calculate after measuring power supply voltage, power supply side current and power supply side
power.
Output side
voltage U2
Across U-V, V-W and
W-U
Rectifier type AC
voltage meter
(Moving-iron type
cannot measure)
Difference between the phases is within ±1% of the
maximum output voltage
Output side
current I2
U, V and W line
currents
Moving-iron type
AC ammeter
Difference between the phases is 10% or lower of
the rated inverter current.
Output side
power P2
U, V, W and U-V,
V-W
Electrodynamic
type single-phase
wattmeter
P2 = W21 + W22
2-wattmeter method (or 3-wattmeter method)
Output side
power factor
Pf2
Calculate in similar manner to power supply side power factor.
Converter
output
Across P/+-N/
−
Moving-coil type
(such as tester)
Inverter LED display is lit.
1.35
×
V1
Tab. 8-7:
Measuring Points and Instruments (1)
Pf1
P1
3
U
1
I1
×
×
---------------------------------
100%
×
=
Pf2
P2
3
U
2
I2
×
×
--------------------------------
100%
×
=
Summary of Contents for FR-A700 EC
Page 2: ......
Page 4: ......
Page 24: ...Description of the Case Product Checking and Part Identification 1 4 ...
Page 38: ...Enclosure design Installation 2 14 ...
Page 774: ...Specifications FR A 740 01800 to 12120 Appendix A 4 ...
Page 820: ...Parameter list with instruction codes Appendix A 50 ...
Page 825: ......