Installation
Enclosure design
FR-A700 EC
2 - 11
Arrangement of multiple inverters
When multiple inverters are placed in the same enclosure, generally arrange them horizontally
as shown in the figure (a). When it is inevitable to arrange them vertically to minimize space, take
such measures as to provide guides since heat from the bottom inverters can increase the tem-
peratures in the top inverters, causing inverter failures.
Placement of ventilation fan and inverter
Heat generated in the inverter is blown up from the bottom of the unit as warm air by the cooling
fan. When installing a ventilation fan for that heat, determine the place of ventilation fan instal-
lation after fully considering an air flow. (Air passes through areas of low resistance. Make an air-
way and airflow plates to expose the inverter to cool air.)
I001006E
Fig. 2-9:
Arrangement of multiple inverters
NOTE
When mounting multiple inverters, fully take caution not to make the ambient temperature of
the inverter higher than the permissible value by providing ventilation and increasing the
enclosure size.
I001007E
Fig. 2-10:
Placement of ventilation fan and inverter
a) Horizontal arrangement
b) Vertical arrangement
Inverter
Inverter
Inverter
Inverter
Inverter
Inverter
Guide
Guide
Guide
Enclosure
Enclosure
Good example!
Inverter
Inverter
Bad example!
Summary of Contents for FR-A700 EC
Page 2: ......
Page 4: ......
Page 24: ...Description of the Case Product Checking and Part Identification 1 4 ...
Page 38: ...Enclosure design Installation 2 14 ...
Page 774: ...Specifications FR A 740 01800 to 12120 Appendix A 4 ...
Page 820: ...Parameter list with instruction codes Appendix A 50 ...
Page 825: ......