Parameter
Selection of operation mode and operation location
FR-A700 EC
6 - 419
External operation mode (Pr. 79 = 0, 2)
Select the external operation mode when performing operation by providing a frequency setting
potentiometer, start switch, etc. externally and connecting them to the control circuit terminals
of the inverter.
Basically, parameter changing is disabled in external operation mode. (Some parameters can
be changed. Refer to Tab. 6-1 for the parameter list.)
When "0" or "2" is selected for Pr. 79, the inverter enters the external operation mode at power
on. (When using the network operation mode, refer to section 6.22.2.)
If you don’t need to change the parameter settings frequently you can set the unit to external
mode permanently by setting Pr. 79 to "2". (If you need to change parameter settings frequently
external mode should be activated by setting Pr. 79 to "0". Then the frequency inverter will switch
to external mode automatically when the power is switched on but it can be switched to PU mode
by pressing the PU/EXT key. You can then make the parameter changes in PU mode and switch
back to external mode again afterwards by pressing PU/EXT again.)
The STF and STR signal are used as a start command, and the terminal 2, 4, multi-speed set-
ting, JOG signal, etc. are used as frequency setting.
Fig. 6-205:
External operation mode
I001205E
Motor
Power supply
Forward rotation
start
Reverse rotation
start
Frequency setting
potentiometer
Inverter
Summary of Contents for FR-A700 EC
Page 2: ......
Page 4: ......
Page 24: ...Description of the Case Product Checking and Part Identification 1 4 ...
Page 38: ...Enclosure design Installation 2 14 ...
Page 774: ...Specifications FR A 740 01800 to 12120 Appendix A 4 ...
Page 820: ...Parameter list with instruction codes Appendix A 50 ...
Page 825: ......