Parameter
Selection of operation mode and operation location
FR-A700 EC
6 - 427
6.22.2
Operation mode at power on (Pr. 79, Pr. 340)
When power is switched on or when power comes back on after instantaneous power failure, the
inverter can be started up in network operation mode.
After the inverter has started up in the network operation mode, parameter write and operation
can be performed from a program.
Set this mode for communication operation using the inverter RS-485 terminals or communi-
cation option.
The above parameters can be changed during a stop in any operation mode.
The parameters can be set whenever the communication option is connected. (Refer to
section 6.21.4.)
Pr.
No.
Name
Initial
Value
Setting
Range
Description
Parameters referred to
Refer to
Section
79
Operation mode
selection
0
0–4/6/7
Select the operation mode.
(Refer to page 6-418.)
57
79
Restart coasting
time
Operation mode
selection
340
Communication
start-up mode
selection
0
0
As set in Pr. 79.
1/2
Started in network operation mode.
When the setting is "2", it will resume the
pre-instantaneous power failure opera-
tion mode after an instantaneous power
failure occurs.
10/12
Started in network operation mode.
Operation mode can be changed between
the PU operation mode and network
operation mode from the operation
panel. When the setting is "12", it will
resume the pre-instantaneous power fail-
ure operation mode after an instantane-
ous power failure occurs.
Summary of Contents for FR-A700 EC
Page 2: ......
Page 4: ......
Page 24: ...Description of the Case Product Checking and Part Identification 1 4 ...
Page 38: ...Enclosure design Installation 2 14 ...
Page 774: ...Specifications FR A 740 01800 to 12120 Appendix A 4 ...
Page 820: ...Parameter list with instruction codes Appendix A 50 ...
Page 825: ......