Simple mode parameter list
Basic settings
5 - 26
Setting
Set "1" or "101" in Pr. 96 "Auto tuning setting/status".
●
When the setting is "1"
Tuning is performed without motor running. It takes approximately 25 to 120s* until tuning
is completed. (Excitation noise is produced during tuning.)
(* Tuning time differs according to the inverter capacity and motor type.)
●
When the setting is "101"
Tuning is performed without motor running. It takes approximately 40s until tuning is
completed. The motor runs at nearly its rated frequency.
Set the rated voltage of motor in Pr. 83 "Motor rated voltage" and rated frequency of motor in
Pr. 84 "Rated motor frequency".
Set Pr. 71 "Applied motor" according to the motor used.
For other settings of Pr. 71 , refer to section 6.12.2.
Motor
Pr. 71
Mitsubishi standard motor,
Mitsubishi high efficiency motor
SF-JR, SF-TH
3
SF-JR 4P-1.5kW or less
23
SF-HR
43
Others
3
Mitsubishi constant-torque motor
SF-JRCA 4P, SF-TH (constant-
torque)
13
SF-HRCA 4P
53
Others (SF-JRC, etc.)
13
Vector control dediated motor
SF-V5RU, SF-THY
33
Other manufacturer's standard motor —
3
Other manufacturer's constant-
torque motor
—
13
Tab. 5-3:
Motor selection