Parameter
Adjust the output torque of the motor (current)
FR-A700 EC
6 - 161
Fig. 6-53:
Stall prevention level, when the set frequency
exceeds the value of Pr. 49 (Pr. 115)
I001123E
Fig. 6-54:
Stall prevention level, when the set frequency
is equal to or less than the value of Pr. 49
(Pr. 115)
I001124E
NOTES
When Pr. 49
≠
9999 (level changed according to frequency) and Pr. 48 = 0%
The stall prevention operation level is 0% at or higher than the frequency set in Pr. 49.
In the initial setting, the RT signal is assigned to the RT terminal. By setting "3" to any of
Pr. 178 to Pr. 189 "Input terminal function selection", you can assign the RT signal to the
other terminal.
Changing the terminal assignment using Pr. 178 to Pr. 189 "Input terminal function selec-
tion" may affect the other functions. Please make setting after confirming the function of
each terminal.
The RT (X9) signal acts as the second (third) function selection signal and makes the other
second functions valid.
Pr. 22
used
Time
Stall
prevention
level
Output
frequency [Hz]
Pr. 49
Output frequency
Set
frequency
Pr. 48
used
f
set
> Pr. 49 (Pr. 115)
Pr. 22
used
Time
Stall
prevention
level
Output
frequency [Hz]
Pr. 49
Output frequency
Set
frequency
Pr. 48
used
f
set
≤
Pr. 49 (Pr. 115)
Summary of Contents for FR-A700 EC
Page 2: ......
Page 4: ......
Page 24: ...Description of the Case Product Checking and Part Identification 1 4 ...
Page 38: ...Enclosure design Installation 2 14 ...
Page 774: ...Specifications FR A 740 01800 to 12120 Appendix A 4 ...
Page 820: ...Parameter list with instruction codes Appendix A 50 ...
Page 825: ......