Selection of operation mode and operation location
Parameter
6 - 424
Switching of operation mode by external terminal (X16)
When external operation and operation from the operation panel are used together, use of the
PU-external operation switching signal (X16) allows switching between the PU operation mode
and external operation mode during a stop (during a motor stop, start command off).
When Pr. 79 = any of "0, 6, 7", the operation mode can be switched between the PU operation
mode and external operation mode. (Pr. 79 = 6 switch-over mode can be changed during oper-
ation)
For the terminal used for X16 signal input, set "16" to any of Pr. 178 to Pr. 189 "Input terminal
function selection" to assign the function.
Pr. 79
X16 Signal State Operation Mode
Remarks
ON (external)
OFF (PU)
0 (initial value)
External operation
mode
PU operation mode
Can be switched to external, PU or NET
operation mode
1
PU operation mode
Fixed to PU operation mode
2
External operation mode
Fixed to external operation mode (Can be
switched to NET operation mode)
3 / 4
External/PU combined operation mode
External/PU combined mode fixed
6
External operation
mode
PU operation mode
Can be switched to external, PU or NET
operation mode with operation continued
7
X12 (MRS) ON
External operation
mode
PU operation mode
Can be switched to external, PU or NET
operation mode (Output stop in external
operation mode)
X12 (MRS) OFF
External operation mode
Fixed to external operation mode (Forcibly
switched to external operation mode.)
Tab. 6-121:
Operation mode switching by signal X16
NOTES
The operation mode status changes depending on the setting of Pr. 340 "Communication
start-up mode selection" and the ON/OFF states of the X65 and X66 signals. (For details,
refer to page 6-425.)
The priorities of Pr. 79, Pr. 340 and signals are:
Pr. 79 > X12 > X66 > X65 > X16 > Pr. 340
Changing the terminal assignment using Pr. 178 to Pr. 189 "Input terminal function selec-
tion" may affect the other functions. Please make setting after confirming the function of
each terminal.
Summary of Contents for FR-A700 EC
Page 2: ......
Page 4: ......
Page 24: ...Description of the Case Product Checking and Part Identification 1 4 ...
Page 38: ...Enclosure design Installation 2 14 ...
Page 774: ...Specifications FR A 740 01800 to 12120 Appendix A 4 ...
Page 820: ...Parameter list with instruction codes Appendix A 50 ...
Page 825: ......