Parameter
Function assignment of external terminals
FR-A700 EC
6 - 315
6.14.9
Remote output function (REM, Pr. 495 to Pr. 497)
You can utilize the on/off of the inverter’s output signals instead of the remote output terminal of
the programmable logic controller.
The above parameters allow its setting to be changed during operation in any operation
mode even if "0" (initial value) is set in Pr. 77 "Parameter write selection".
The output terminal can be turned on/off depending on the Pr. 496 or Pr. 497 setting. The remote
output selection can be controlled on/off by computer link communication from the PU connector
or RS-485 port or by communication from the communication option.
Set "96" (source logic) or "196" (sink logic) to any of Pr. 190 to Pr. 196 "Output terminal function
selection", and assign the remote output (REM) signal to the terminal used for remote output.
Pr.
No.
Name
Initial
Value
Setting
Range
Description
Parameters referred to
Refer to
Section
495
Remote output
selection
0
0
Remote output data clear at powering off
190–196
Output terminal
function selection
1
Remote output data retention even at
powering off
10
Remote output data clear at powering off
11
Remote output data retention even at
powering off
496
Remote output data 1
0
0–4095
497
Remote output data 2
0
0–4095
Summary of Contents for FR-A700 EC
Page 2: ......
Page 4: ......
Page 24: ...Description of the Case Product Checking and Part Identification 1 4 ...
Page 38: ...Enclosure design Installation 2 14 ...
Page 774: ...Specifications FR A 740 01800 to 12120 Appendix A 4 ...
Page 820: ...Parameter list with instruction codes Appendix A 50 ...
Page 825: ......