Basic operation procedure (JOG operation)
92
4.4
Basic operation procedure (JOG operation)
4.4.1
Performing JOG operation using external
signals
POINT
POINT
• Perform JOG operation only while the JOG signal is ON.
• Use
Pr.15 Jog frequency
and
Pr.16 Jog acceleration/deceleration time
for the operation.
• Set
Pr.79 Operation mode selection
= "2" (External operation mode).
[Connection diagram]
NOTE
• To change the frequency, change
Pr.15 Jog frequency
(initial value "5 Hz").
• To change the acceleration/deceleration time, change
Pr.16 Jog acceleration/deceleration time
(initial value "0.5 s").
Parameters referred to
Pr.15 Jog frequency
Pr.16 Jog acceleration/deceleration time
Pr.79 Operation mode selection
Operation example
Operate at 5 Hz.
Operation
1.
Screen at power-ON
The monitor display appears.
2.
Turning ON the JOG signal
Turn ON the JOG switch (JOG). The inverter is set ready for the JOG operation.
3.
Start
→
acceleration
→
constant speed
Turn ON the start switch (STF or STR). The frequency value on the indication increases in
Pr.16 Jog acceleration/
deceleration time,
and "5.00 Hz" appears. [FWD] indicator is on during the forward rotation, and [REV] indicator is on
during the reverse rotation.
4.
Deceleration
→
stop
Turn OFF the start switch (STF or STR). The frequency value on the indication decreases in
Pr.16 Jog acceleration/
deceleration time,
and the motor stops rotating with "0.00 Hz" displayed. [FWD] or [REV] indicator turns OFF. Turn OFF the
JOG switch (JOG).
STF
Forward rotation start
SD
JOG
Inverter
JOG signal
Reverse rotation start
STR
Switch