(M) Monitor display and monitor output signal
371
5
GROUP
M
Output signal list
• The functions of the output terminals can be set.
• Refer to the following table and set each parameter. (0 to 99: Positive logic, 100 to 199, 300 to 399: Negative logic)
Setting
Signal
name
Function
Operation
Related
parameter
Refer
to
page
Positive
logic
Negative
logic
0
100
RUN
Inverter running
Output during operation when the inverter output
frequency reaches
Pr.13 Starting frequency
or
higher.
―
1
101
SU
Up to frequency
Output when the output frequency reaches the set
frequency.
Pr.41
2
102
IPF
Instantaneous power failure/
undervoltage
Output when an instantaneous power failure or
undervoltage protection operation occurs.
Pr.57
3
103
OL
Overload warning
Output during operation of the stall prevention
function.
Pr.22, Pr.23, Pr.66,
Pr.148, Pr.149,
Pr.154
4
104
FU
Output frequency detection
Output when the output frequency reaches the
frequency set in
Pr.42
(
Pr.43
during reverse
rotation) or higher.
Pr.42, Pr.43
5
105
FU2
Second output frequency
detection
Output when the output frequency reaches the
frequency set in
Pr.50
or higher.
Pr.50
6
106
FU3
Third output frequency
detection
Output when the output frequency reaches the
frequency set in
Pr.116
or higher.
Pr.116
7
107
RBP
Regenerative brake pre-
alarm
Output when 85% of the regenerative brake duty
set in
Pr.70
is reached.
Pr.70
8
108
THP
Electronic thermal O/L relay
pre-alarm
Output when the cumulative electronic thermal O/
L relay value reaches 85% of the trip level.
(Electronic thermal O/L relay protection (E.THT/
E.THM) is activated when the value reaches
100%.)
Pr.9
10
110
PU
PU operation mode
Output when PU operation mode is selected.
Pr.79
11
111
RY
Inverter operation ready
Output when the reset process is completed after
powering ON the inverter (when starting is
possible by switching the start signal ON or during
operation).
―
12
112
Y12
Output current detection
Output when the output current is higher than the
Pr.150
setting for the time set in
Pr.151
or longer.
Pr.150, Pr.151
13
113
Y13
Zero current detection
Output when the output current is lower than the
Pr.152
setting for the time set in
Pr.153
or longer.
Pr.152, Pr.153
14
114
FDN
PID lower limit
Output when the value is lower than the lower limit
of PID control.
Pr.127 to Pr.134,
Pr.575 to Pr.577
15
115
FUP
PID upper limit
Output when the value is higher than the upper
limit of PID control.
16
116
RL
PID forward/reverse rotation
output
Output during forward rotation under PID control.
17
―
MC1
Electronic bypass MC1
Used when using the electronic bypass function.
Pr.135 to Pr.139,
Pr.159
18
―
MC2
Electronic bypass MC2
19
―
MC3
Electronic bypass MC3
20
120
BOF
Brake opening request
Output to open the brake when the brake
sequence function is selected.
Pr.278 to Pr.285,
Pr.292
22
122
BOF2
Second brake opening
request
Output to open the brake when the second brake
sequence function is selected (RT signal ON).
Pr.641 to Pr.649,
Pr.292
25
125
FAN
Fan fault output
Output when a fan fault occurs.
Pr.244
26
126
FIN
Heat sink overheat pre-
alarm
Output when the heat sink temperature reaches
about 85% of the heat sink overheat protection
operation temperature.
―
27
127
ORA
Orientation complete
(for vector control
compatible option)
When orientation is enabled.
Pr.350 to Pr.366,
Pr.369, Pr.393,
Pr.396 to Pr.399
28
128
ORM
Orientation fault
(for vector control
compatible option)