(M) Monitor display and monitor output signal
358
Monitor description list (Pr.54, Pr.158)
• Set
Pr.54 FM terminal function selection
for the monitor to be output to the terminal FM (pulse train output).
• Set
Pr.158 AM terminal function selection
for the monitor to be output to the terminal AM (analog voltage
output). Output with a negative sign can be made (-10 VDC to +10 VDC) from the terminal AM.
in the [Negative (-)
output] indicates the output value is negative at the terminal AM. (For setting of the output with/without minus sign, refer to
• Refer to the following table and set the monitor to be displayed. (Refer to
for the monitor description.)
Monitor item
Increment
and unit
Pr.54 (FM)
Pr.158 (AM)
setting
Terminal FM/AM
Full-scale value
Negative
(-) output
REMARKS
Output frequency
0.01 Hz
1
Pr.55
Output current
2
Pr.56
Output voltage
0.1 V
3
1000 V
Frequency setting value
0.01 Hz
5
Pr.55
Running speed
1 (r/min)
6
Value is
Pr.55
converted
by
Pr.37, Pr.144
. (Refer
to
.)
Refer to
running speed monitor.
Motor torque
0.1%
7
Pr.866
Converter output voltage
0.1 V
8
1000 V
0.1%
9
Brake duty decided by
Pr.30
and
Pr.70
.
Electronic thermal O/L
relay load factor
0.1%
10
Electronic thermal O/L
relay operation level
(100%)
Output current peak value
0.01 A/0.1 A
11
Pr.56
Converter output voltage
peak value
0.1 V
12
1000 V
Input power
0.01 kW/
0.1 kW
13
Inverter rated power
2
Output power
0.01 kW/
0.1 kW
14
Inverter rated power
2
Load meter
0.1%
17
Pr.866
Motor excitation current
0.0 1 A/0.1 A
18
Pr.56
Reference voltage output
—
21
—
Terminal FM:
1440 pulses/s is output when
Pr.291
= 0,1.
50k pulses/s is output when
Pr.291
≠
0,1.
Terminal AM: output is 10 V.
Motor load factor
0.1%
24
200%
Torque command
0.1%
32
Pr.866
Torque current command
0.1%
33
Pr.866
Motor output
0.01 kW/
0.1 kW
34
Rated motor capacity
Torque monitor (power
driving/regenerative
driving polarity switching)
0.1%
36
Pr.866
—
—
46
—
For manufacturer setting. Do
not set.
Energy saving effect
Changeable by
parameter
setting
50
Inverter capacity
Regarding the energy saving
monitor, refer to
PID set point
0.1%
52
100%
Refer to
control.
PID measured value
0.1%
53
100%
PID deviation
0.1%
54
100%
Output with a negative sign
(terminal AM)
Motor thermal load factor
0.1%
61
Motor thermal
operation level (100%)
Inverter thermal load
factor
0.1%
62
Inverter thermal
operation level (100%)
PID measured value 2
0.1%
67
100%