Causes and corrective actions
635
6 5
Alarm
Output is not shut off when a protective function activates. An alarm can also be output with a parameter setting.
(Set "98" in
Pr.190 to Pr.196 (Output terminal function selection).
.)
Fault
When a protective function activates, the inverter trips and a fault signal is output.
Abbreviation
FN
FR-LU08
FR-PU07
FN
Name
Fan alarm
Description
For the inverter that contains a cooling fan, FN appears on the operation panel when the cooling fan stops
due to a fault, low rotation speed or different operation from the setting of
Pr.244 Cooling fan operation
selection
.
Check point
Check the cooling fan for a failure.
Corrective action
The fan may be faulty. Please contact your sales representative.
Abbreviation
E.OC1
FR-LU08
FR-PU07
OC During Acc
Name
Overcurrent trip during acceleration
Description
When the inverter output current reaches or exceeds approximately 235%
of the rated current during
acceleration, the protection circuit is activated and the inverter trips.
Check point
• Check for sudden speed acceleration.
• Check if the downward acceleration time is too long in a lift application.
• Check for output short-circuit.
• Check that the
Pr.3 Base frequency
setting is not 60 Hz when the motor rated frequency is 50 Hz.
• Check if the stall prevention operation level is set too high. Check if the fast-response current limit operation
is disabled.
• Check that the regenerative driving is not performed frequently. (Check if the output voltage becomes larger
than the V/F reference voltage at regenerative driving and overcurrent occurs due to increase in the motor
current.)
• Check that the power supply for RS-485 terminal is not shorted (under vector control).
• Check that the encoder wiring and the specifications (encoder power supply, resolution, differential/
complementary) are correct. Check also that the motor wiring (U, V, W) is correct (under vector control).
• Check that the rotation direction is not switched from forward to reverse rotation (or from reverse to forward)
during torque control under Real sensorless vector control.
• Check that the inverter capacity matches with the motor capacity. (PM sensorless vector control)
• Check if a start command is given to the inverter while the motor is coasting. (PM sensorless vector control)
Corrective action
• Set the acceleration time longer. (Shorten the downward acceleration time of the lift.)
• If "E.OC1" always appears at start, disconnect the motor once and restart the inverter.
If "E.OC1" still appears, contact your sales representative.
• Check the wiring to make sure that output short circuit does not occur.
• Set 50 Hz in
Pr.3 Base frequency
. (Refer to
.)
• Lower the stall prevention operation level. Activate the fast-response current limit operation.
(Refer to
• Set the base voltage (rated voltage of the motor, etc.) in
Pr.19 Base frequency voltage
.
(Refer to
.)
• Check RS-485 terminal connection (under vector control).
• Check the wiring and specifications of the encoder and the motor. Perform the setting according to the
specifications of the encoder and the motor (under vector control). (Refer to
• Prevent the motor from switching the rotation direction from forward to reverse (or from reverse to forward)
during torque control under Real sensorless vector control.
• Choose inverter and motor capacities that match. (PM sensorless vector control)
• Input a start command after the motor stops. (PM sensorless vector control)
Differs according to ratings. The rating can be changed using
Pr.570 Multiple rating setting
. (Refer to
.)
148% for SLD rating, 170% for LD rating, 235% for ND rating (initial setting), and 280% for HD rating